ENVIRO-TEC
29
SECTION 2 - START-UP
FORM ET115.24-NOM4 (819)
2
3.
Low Speed Adjust:
Set Configuration Switch
to LOW SPEED adjust (see
Figure 18 on page
29
). Switches to ON-OFF-OFF-OFF-ON-OFF-
OFF-OFF
• Set switch 1 to ON (Program).
• Set switches 2 -4 to OFF.
• Set switch 5 to ON (Lo/Min).
• Set switches 6 through 8 to OFF.
• Refer to voltmeter connected to TP1 and
TP3. Using an insulated 1/8” flat bladed
screwdriver, adjust speed potentiometer to
desired high speed airflow per Fan Calibra-
tion Curve on unit.
•
STORE:
Set switch 8 to Store (ON), wait
one second, then to Set (OFF), to save the
value.
FIGURE 18 -
LOW SPEED ADJUST
4.
Resume Normal Three Speed Operation:
Set
all switches to OFF to resume normal three speed
operation. Refer to
Figure 19 on page 29
.
FIGURE 19 -
NORMAL THREE SPEED OPERATION
2 – 10 VDC PROPORTIONAL MOTOR
CONTROL
Speed range adjustment for Proportional Control op-
eration. Minimum (Min) and maximum (Max) speeds
are programmed at the factory for optimum opera-
tion. Changing factory Min or Max speed defaults will
change the motor effective speed range and invalidate
the voltage settings shown on the Fan Calibration
Curve. However, the speed range may still be adjusted
as long as the Min speed remains greater than 70 CFM/
kW for units with electric heat.
Thermostat must be set for either analog
or single (high) speed operation.
1.
Connections:
Connect or verify connection of
remote analog signal and common wires to 2-10
VDC Remote Control Input terminals (refer to
Figure 12 on page 25
).
2.
Set Mode to 2 – 10 VDC Proportional Con-
trol:
Set configuration switches to 2 – 10 ANA
-
LOG programming mode (see
Figure 20 on page
30
). Switches to ON-ON-OFF-OFF-OFF-ON-
OFF-OFF.
• Set switch 1 to ON (Program).
• Set switch 2 to ON (Analog).
• Set switches 3 – 5 to OFF.
• Set switch 6 to ON (2-10 V).
Summary of Contents for VHA
Page 10: ...ENVIRO TEC 10 FORM ET115 24 NOM4 819 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 41: ...ENVIRO TEC 41 SECTION 2 START UP FORM ET115 24 NOM4 819 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 54: ...ENVIRO TEC 54 FORM ET115 24 NOM4 819 SECTION 6 Dimensional Data 74 80083 ...
Page 78: ...ENVIRO TEC 78 FORM ET115 24 NOM4 819 SECTION 6 Dimensional Data NOTES ...