ENVIRO-TEC
36
FORM ET115.24-NOM4 (819)
SECTION 2 - START-UP
TABLE 3 -
SIGNAL CONNECTOR
PIN
DESCRIPTION
1
C1 (n/u - com)
2
W/W1 (n/u)
3
C2 (PWM COM)
4
DELAY (n/u)
5
COOL (n/u)
6
Y1 (n/u)
7
ADJUST (n/u)
8
OUT - (PWM FB)
9
O (n/u)
10
PWM
11
HEAT (n/u)
12
R (n/u)
13
EM/W2 (n/u)
14
Y/Y2 (n/u)
15
G (Fan Enable)
16
OUT + (PWM FB)
NOTE:
Connections marked (n/u) are not used.
TABLE 4 -
POWER CONNECTOR
PIN
DESCRIPTION
1
Jumper pin 1 to pin 2 for 120 VAC Line
Input only
2
3
Chassis Ground
4
AC Line (Line 1)
5
AC Line (Line 2, Neutral)
LD19310
LD19311
Constant RPM EC Motors
FIGURE 26 -
CONSTANT RPM EC MOTOR (1/4 HP
SHOWN)
FIGURE 27 -
CONSTANT RPM EC MOTOR DRIVER
TABLE 5 -
CON1, POWER INPUT
PIN
DESCRIPTION
1
Ground
2
Neutral (or Line 2)
3
Line 1
TABLE 6 -
CON502 (IF PRESENT), PROGRAM-
MING CONNECTOR
PIN
DESCRIPTION
1
+15V
2
Ground
3
TX-
4
TX+
TABLE 7 -
CON302, PWM SIGNAL INPUT
PIN
DESCRIPTION
4
Speed Control Input (H)
3
Speed Control Input (L)
2
Speed Control Input (H)
1
Speed Control Input (L)
LD19314
LD19313
LD19312
Summary of Contents for VHA
Page 10: ...ENVIRO TEC 10 FORM ET115 24 NOM4 819 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 41: ...ENVIRO TEC 41 SECTION 2 START UP FORM ET115 24 NOM4 819 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 54: ...ENVIRO TEC 54 FORM ET115 24 NOM4 819 SECTION 6 Dimensional Data 74 80083 ...
Page 78: ...ENVIRO TEC 78 FORM ET115 24 NOM4 819 SECTION 6 Dimensional Data NOTES ...