ENVIRO-TEC
37
SECTION 2 - START-UP
FORM ET115.24-NOM4 (819)
2
TABLE 8 -
CON503 (IF PRESENT), MOTOR EN-
ABLE INPUT
PIN
DESCRIPTION
1
No Connection
2
Signal Input
3
Ground
TABLE 9 -
CON202, FEEDBACK FROM EC MOTOR
HALL SENSOR
PIN
DESCRIPTION
1
+5V
2
Ground
3
Hall "W"
4
Hall "V"
5
Hall "U"
TABLE 10 -
CON201, OUTPUT POWER TO MOTOR
PIN
DESCRIPTION
1
W1
2
NC
3
V1
4
U1
Constant RPM EC Motor Driver Enable
Jumper
The ETI Constant RPM EC motor driver has a Mo-
tor Enable Input. These drivers require a jumper across
the Enable Connector to allow the unit to operate. See
Figure 10 for jumper location across pins 2 and 3 of the
Enable Connector.
FIGURE 28 -
CONSTANT RPM EC DRIVER EC
MOTOR ENABLE CONNECTOR
LD19308