5
Three Phase Delta Installation
1.
Connect black phase A to phase A of the 30 A breaker.
2.
Next connect black phase B to phase B of 30 A breaker.
3.
Then connect black phase C to phase C of 30 A breaker.
4.
Last connect green ground to ground bus bar or panel. Ground is case ground only
and should NOT be connected to neutral bus bar.
THREE PHASE DELTA
PRODUCTS
EP-2000
EP-2500
VOLTAGE
ID#
MCOV
3D240
264V
3D480
528V
Three Phase High Leg Delta Installation
1.
Connect black phase A to phase A of the 30 A breaker.
2.
Next connect red phase B to phase B of the 30 A breaker.
WARNING: Please confirm that phase B is the HIGH LEG
3.
Then connect black phase C to phase C of the 30 A breaker.
4.
Last connect green ground to ground bus bar or panel. Ground is case ground only
and should NOT be connected to neutral bus bar.
3 PHASE HL DELTA
PRODUCTS
EP-2000
EP-2500
VOLTAGE
ID#
MCOV
3H240
132V
234V
L1
L2
L3
3 Phase Delta 3 Wire
L3
L1
L2
3 Phase Delta 3 Wire
N
3 phase delta 3 wire
3 phase delta 3 wire + neutral