Automatic Air Dehydrator
ADH
®
SIROCCO™
Instruction Manual
3.
The first line, View Cfg, should already be highlighted. Press the middle of
the rocker switch to select it. Now, you will see the Function screen.
Refer to Figure 48.
Figure 48. THE FUNCTION SCREEN.
4.
The first line, Operat’n, should already be highlighted. Press the middle of
the rocker switch to select it. The View Operational Settings screen will
appear. Refer to Figure 49.
Figure 49. THE VIEW OPERATIONAL SETTINGS SCREEN.
5.
You will notice that on the View Operational Settings screen, there are no
highlighted lines. This is because this is not the screen used to change
the operational settings, but only to view them.
6.
While the operational settings are displayed, it is recommended that you
write them down as a quick reference and retain them in should any of the
settings ever be lost or accidentally changed and it becomes necessary to
restore them.
7.
Once you have viewed the settings, press the rocker switch as prompted
by the Hit a key prompt at the bottom of the screen and the Function
screen will appear.
Operat’n
Alarms
Display
Return
UNIT English
LALM 0.15
LLIM 0.30
HLIM 0.50
HLRM 1.50
Hum Sensor
Y
Hit a key
Low Alarm
Low Limit
High Limit
High Alarm
These are
the factory
default
settings.