24431
Rev. A
10/12
http: www.networketi.com
Environmental Technology, Inc.
83 of 94
Automatic Air Dehydrator
ADH
®
SIROCCO™
Instruction Manual
CONTROL
Maximum Pressure
Configurable Range:
0.20 psig to 7.5 psig (14 mbar to 517 mbar),
Default: 0.50 psig (34.5 mbar)
Minimum Pressure
Configurable Range:
0.10 psig to 7.4 psig (7 mbar – 510 mbar),
Default: 0.30 psig (21 mbar)
Low Pressure
Alarm Level
User-Configurable, Default: 0.15 psig (10 mbar)
High Pressure
Alarm Level
User-Configurable, Default 1.5 psig (103.5 mbar)
Alarm Relays
Contact Type: Form C, SPDT, reverse acting
Ratings: 0.25 Amps @ 60 V
User-Configurable, Defaults:
Defaults: Alarm Relay 1: Summary Alarm
Alarm Relay 2: Low Pressure Alarm
Alarm Relay 3: Dew Point Alarm (User-Configurable)
Duty Cycle Alarm
Default: 50% (User-Configurable)
ENVIRONMENTAL
Operating
Temperature
32°F to 113°F (0°C to 45°C)
Storage
Temperature
−
40°F to 150°F (
−
40°C to 60°C)