27
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Pressure Drop
Dual Capacity
Model
GPM
Pressure Drop (psi)
30°F
50°F
70°F
90°F
110°F
026
full
load
4
1.4
1.3
1.2
1.1
1.0
6
2.8
2.6
2.4
2.3
2.1
8
4.7
4.4
4.1
3.8
3.5
10
7.0
6.6
6.2
5.8
5.3
026
part
load
3
0.8
0.7
0.7
0.7
0.6
5
2.0
1.8
1.7
1.6
1.5
7
3.6
3.4
3.2
3.0
2.8
9
5.8
5.5
5.1
4.8
4.4
038
full
load
5
1.2
1.2
1.1
1.0
1.0
7
2.2
2.1
1.9
1.8
1.7
9
3.4
3.2
3.0
2.8
2.6
11
4.9
4.6
4.3
4
3.7
038
part
load
4
0.9
0.8
0.8
0.7
0.7
6
1.7
1.6
1.5
1.4
1.3
8
2.8
2.6
2.5
2.3
2.1
10
4.2
3.9
3.7
3.4
3.2
049
full
load
6
1.2
1.2
1.1
1.0
1.0
9
2.4
2.2
2.1
2.0
1.8
12
3.9
3.6
3.4
3.2
2.9
15
5.7
5.3
5
4.7
4.3
049
part
load
5
0.9
0.9
0.8
0.8
0.7
8
2.0
1.8
1.7
1.6
1.5
11
3.4
3.1
2.9
2.8
2.5
14
5.0
4.7
4.4
4.1
3.8
064
full
load
8
1.8
1.7
1.6
1.4
1.3
12
3.8
3.5
3.3
3.0
2.8
16
6.5
6.0
5.6
5.2
4.8
20
9.7
9.1
8.5
8.0
7.4
064
part
load
6
1.0
0.9
0.9
0.8
0.8
10
2.6
2.5
2.3
2.1
2.0
14
5.0
4.7
4.4
4.1
3.8
18
8.1
7.6
7.1
6.6
6.1
072
full
load
12
3.2
3.0
2.8
2.6
2.4
15
4.5
4.2
4.0
3.7
3.4
18
6.0
5.7
5.3
4.9
4.6
21
7.8
7.3
6.8
6.4
5.9
072
part
load
10
2.3
2.1
2.0
1.9
1.7
13
3.6
3.3
3.0
2.8
2.6
16
5.0
4.6
4.3
4.0
3.7
19
6.5
6.2
5.8
5.4
5.0
5/30/06
Compressor Resistance
Compressor Resistance Chart (Ohms)
Model
208-230/60/1
Run
Start
026
1.23-1.30
1.41-1.50
038
.829-.954
1.19-1.38
049
.590-.679
1.41-1.62
064
.455-.524
.558-.643
072
.344-.395
.495-.570
1/13/11
Thermistor Resistance Chart
Thermistor
Temperature (°F)
Microprocessor
Resistance (Ohms)
5
75757-70117
14
57392-53234
23
43865-40771
32
33809-31487
41
26269-24513
50
20570-19230
59
16226-15196
68
12889-12093
77
10310-9688
86
8300-7812
95
6723-6337
104
5480-5172
113
4490-4246
122
3700-3504
131
3067-2907
140
2554-2424
149
2149-2019
7/6/10
Thermistor Resistance