To be connected by a qualified electrician:

Drill an approx. 10 mm hole in the cabin wall near the entry area of the stove‘s connecting cable. 

Feed the connecting cable through the borehole to the outside and connect to the power supply 

in a distribution box suitable for wet rooms.
Please observe the wiring diagram and the regulations of the local power supplier (TAB 2000) and 

the VDE

.

 

Caution! An adequate fuse and a mains circuit breaker must be installed in the stove‘s 

power cable on site.

Connection example for 400V 3N AC

4,5 kW  = 3x 1500 W

6,0 kW  = 3x 2000 W

7,5 kW  = 3x 2500 W

Power acc. DIN

Electrical connection

Fuse protection

 

Connecting cable 

main - heater

4,5 kW

400 V 3N AC 50 Hz

3 x 16 A

5 x 1,5 mm²

6,0 kW

7,5 kW

All cross sections of a line are minimum diameters in mm² (Copper line).

A1

A2

A3

B1

B2

B3

Thermostat

Sicherheits

temperaturbegrenzer

M

  

Zeitschaltuhr

timer

Thermostat

overheat safty 

shutdown device

reset

A1

A1

B1

B

A

A

M

U V W N N

PE

(Gr)

N

X Y Z

Saunaheizgerät / 

sauna heater

poêle de sauna / печь сауны

max. 7,5 kW

rot

grün

green

red

Netz/mains

400 V 3N AC

5x 1,5mm²

max. 10 m

Specifications for default connection 400V 3N AC

!

 Caution!

  Make sure to connect the neutral wire N.

Summary of Contents for Filius Control

Page 1: ...INNOVATIVE SAUNA TECHNOLOGY MADE IN GERMANY Druck Nr 29345062 en 18 19 Filius Control 400 V 3N AC 230 V 1N AC EN Installlation and operating instruction...

Page 2: ...ications 6 Connection example 400 V 3N 8 Connection example 230 V 1N 9 Installation of the Filius Control 10 Minimum distances 10 Commissioning 12 Position change control panel left right 13 Replaceme...

Page 3: ...pped the goods Please note that you will only be able to achieve anoptimumsaunaclimateifthecabinwithitsair intake and ventilation the sauna heater and the control unit are aligned to each other Please...

Page 4: ...eofsuitable low resin untreatedmaterials e g spruce Only a sauna heater with the appropriate power output may be installed in the sau na cabin Please provide air intake and vent ope nings in each saun...

Page 5: ...floor On heaters with bases this clearance is maintained via the base or legs of the device Floor heating in the sauna cabin increases the surface temperature of the flooring Please see the dimension...

Page 6: ...able exits the sauna heater and guide this cable outside through the hole to the control unit The cable and all other connecting cables mains power cables and cabin lighting should be installed in ins...

Page 7: ...AC Anschluss an 230V 1NWechselstrom m glich Power rating 4 5 kW 6 0 kW 7 5 kW For sauna size 4 6 m 6 8 m 7 10 m Min size air inlet and exhaust vent 35 x 11 cm Weight without stones and packing 15 kg...

Page 8: ...ite Connection example for 400V 3N AC 4 5 kW 3x 1500 W 6 0 kW 3x 2000 W 7 5 kW 3x 2500 W Power acc DIN Electrical connection Fuse protection Connecting cable main heater 4 5 kW 400V 3N AC 50 Hz 3 x 16...

Page 9: ...re given for 230V 1N power supply Specifications for 230V 1N connection 4 5 kW 3x 1500 W 6 0 kW 3x 2000 W 7 5 kW 3x 2500 W A1 A2 A3 B1 B2 B3 Thermostat Sicherheits temperaturbegrenzer M Zeitschaltuhr...

Page 10: ...all so that there is approx 3 mm space between the wall and the head of the screw Fig 2 2 berpr fen Sie dass die Zuleitung span nungslos ist um die Ofenzuleitung an zuschlie en First unscrew the four...

Page 11: ...and the two lock screws U V W N N PE N Z Y X L N PE 230V AC A Strahlblech U V W N N PE N Z Y X 400V 3N AC Fig 4 1 Connection line Screws 4 2 x 9 5 Corrugated head screws 2 9 x 19 Connection terminal...

Page 12: ...necessary The design of the cabin can impact on the way the cabin heats up and cause tem perature differences of up to 15 C Also many bimetal thermometers wall moun ted react sluggishly so that the re...

Page 13: ...13 EN Position change control panel left right safety screw 2 9 x 19 Fig 1 Fig 2 Fig 3 Fig 5 Fig 4 2 1 6 180 4 7 8 9 3 10 5...

Page 14: ...14 EN Replacement of heating elements Fig 1 Fig 2 Fig 4 Fig 3 1 3 2 6 7 4 5...

Page 15: ...more essences or volatile oils than advised on the packaging Never use alcohol or undiluted concentrates Cau tion Fire hazard All sauna heating units are made of low corro sion material To enjoy your...

Page 16: ...l units will be protected by this ELCB Under current manufacturing technology it is not reasonable to use heating elements for sau na heaters which do not collect moisture from the surrounding air It...

Page 17: ...your questions quickly and compe tently please provide the information printed on the type shield including the model item no and serial no in all inquiries Equipment commissioning date ______________...

Page 18: ...roducts is designed for the ship ping of individually packed goods pallet We expressly point out that our packaging is not suitable for individual shipments via parcel post The manufacturer shall acce...

Reviews: