Error Message
Possible cause
Fault elimination
Error
Error text
243
THROTTLE
PROG.
A wrong profile has been set in the
throttle profile.
Set properly the throttle-related
parameters.
187
LIFT + LOWER
Both the pump requests (LIFT and
LOWER) are active at the same
time.
- Check that LIFT and LOWER
requests are not active at the
same time.
- Check the LIFT and LOWER
input states through the TESTER
function.
- Check the wirings.
- Check if there are failures in the
micro-switches.
228
TILLER OPEN
Tiller/seat input has been inactive
for more than 30 seconds.
- Activate the tiller/seat input.
- Check the tiller/seat input state
through the TESTER function.
- Check the wirings.
252
WRONG ZERO
At start-up the amplifiers used to
measure the motor voltage sense
voltages above 3 V or below 2 V.
This type of fault is not related to
external components. Replace
the logic board.
250
THERMIC SENS.
KO
The output of the controller thermal
sensor is out of range.
This kind of fault is not related to
external components. Replace
the controller.