Page 30
EPS Stromversorgung GmbH
Alter Postweg 101 • 86159 Augsburg
Germany
ELR 9000 Series
Fon: +49 821 / 570451-0
Fax: +49 821 / 570451-25
2.3.5 Connection to DC sources
In the case of a device with a high nominal current and hence a thick and heavy DC connec-
tion cable it is necessary to take account of the weight of the cable and the strain imposed
on the DC connection. Especially when mounted in a 19” cabinet or similar, where the cable
hangs on the DC input, a strain reliever has to be used.
The DC load input is on the back side of the device and is
not
protected by a fuse. The cross section of the con-
nection cable is determined by the current consumption, cable length and ambient temperature.
For cables up to 1.5 m and average ambient temperature up to 50 °C, we recommend:
up to
30 A
:
6 mm²
up to
70 A
:
16 mm²
up to
90 A
:
25 mm²
up to
140 A
:
50 mm²
up to
170 A
:
70 mm²
up to
210 A
:
95 mm²
up to
340 A
:
2x70 mm²
up to
510 A
:
2x120 mm²
per connection pole
(multi-conductor, insulated, openly suspended). Single cables of, for example, 70 mm² may
be replaced by 2x35 mm² etc. If the cables are long then the cross section must be increased to avoid voltage
loss and overheating.
2.3.5.1 DC terminal types
The table below shows an overview of the various DC terminals. It is recommended that connection of load cables
always utilizes flexible cables with ring lugs.
Type 1: Models up to 250 V nominal voltage
Type 2: Models from 500 V nominal voltage
M8 bolt on a metal rail
Recommendation: ring connector with a 8 mm hole
M6 bolt on a metal rail
Recommendation: ring connector with a 6 mm hole
2.3.5.2 Cable lead and plastic cover
A plastic cover for contact protection is included for the DC terminal. It should always be installed. The cover for
type 2 (see picture above) is fixed to the connector itself, for type 1 to the back of the device. Furthermore the
cover for type 1 has break outs so that the supply cable can be laid in various directions.
The connection angle and the required bending radius for the DC cable must be taken into
account when planning the depth of the complete device, especially when installing in a 19”
cabinet or similar. For type 2 connectors only a horizontal lead can be used to allow for instal-
lation of the cover.