28
EN
Operating Guide
PS 800 R Series
Date: 11-22-2012
Applications
Pin assignment and technical specifications of the analogue interface:
Pin
Name
Type
1
Description
Level
Electrical specifications
1
VSEL
AI Set value: Voltage
0….10V correspond to 0….100% of U
nom
2
CSEL
AI Set value: Current
0….10V correspond to 0….100% of I
nom
3
VREF
AO Reference voltage
10V
Accuracy <0.5% at I
max
= 5mA
4
VMON
AO Actual value: current
0….10V correspond to 0….100% of U
nom
5
CMON
AO Actual value: voltage
0….10V correspond to 0….100% of I
nom
6
AGND
Reference for analogue signals
For CMON, VMON
7
Remote
DI Activate external control
External = Low (U
low
<1V),
Internal = High (U
high
>4V)
8
Rem-SB
DI Power output off
Off = Low (U
low
<1V),
On = High (U
high
>4V)
9
OT / OVP
DO Overtemperature OT /
Overvoltage OVP
Low = No error (U
low
<1V)
High = Error (U
high
>4V)
U
max
= 30V, I
max
= 20mA
Quasi Open Collector with
pull-up to +15V
10
DGND
Reference for digital signals
For control and monitoring signals
11
Reserved
X
must not be connected
12
Reserved
X
must not be connected
1)
AO = Analogue output, DI = digital input (no TTL/CMOS), DO = digital output (no TTL/CMOS)
Accuracy 0.2% at I
max
= +2mA
Short-circuit-proof against AGND
U
max
= 30V
I
out
= <1mA at 5V
I
out
= 2mA typ. at 0V
Accuracy <0.5%, U
max
= 12V
Input impedance >100k
6.1 Examples for the analogue interface
6.1.1 Remotely switching output on / off
Input : REM-SB (8)
The input can be used to switch off the device output
at any time. After this, switching it on again is only
possible by releasing the contact or switch.
The contact/switch on pin 8 overrides the pushbutton
„Output On/Off“. It means, if pin 8 „forces“ the output
to be off, it can not be switched on by the pushbutton.
Switching to remote control by pin 7 is not required.
During remote control, this input REM-SB is also
used to acknowledge and reset an OVP error by
pulling the pin to LOW (=off).
6.1.2 Monitoring voltage and current
Analogue outputs: VMON (4) and CMON (5)
The analogue monitoring outputs VMON and CMON
put out 0...10V, which corresponds to 0...100% of
the actual values of voltage and current.
Measuring those output should be done with high-
impedance meters or a high-impedance input of a
measuring circuit, because those outputs can only
drive limited current.
Summary of Contents for PS 8200-70 R
Page 2: ......
Page 11: ...11 Betriebsanleitung PS 800 R Serie DE Stand 22 11 2012 Über das Gerät Bild 4 Seitenansicht ...
Page 17: ......
Page 18: ......
Page 26: ...26 EN Operating Guide PS 800 R Series Date 11 22 2012 About the device Figure 4 Side view ...
Page 30: ...30 EN Operating Guide PS 800 R Series Date 11 22 2012 Applications ...
Page 31: ......
Page 32: ......