Page 16
EPS Stromversorgung GmbH
Alter Postweg 101 • 86159 Augsburg
Germany
PSI 9000 3U Series
Fon: +49 821 / 570451-0
Fax: +49 821 / 570451-25
15 kW
Model 3U
PSI 9200-210 PSI 9360-120 PSI 9500-90
PSI 9750-60
PSI 91500-30
AC Input
Input voltage
340...460 V AC 340...460 V AC 340...460 V AC 340...460 V AC 340...460 V AC
Input connection
3ph,PE
3ph,PE
3ph,PE
3ph,PE
3ph,PE
Input frequency
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
Input fuse (internal)
6x T16 A
6x T16 A
6x T16 A
6x T16 A
6x T16 A
Leak current
< 3.5 mA
< 3.5 mA
< 3.5 mA
< 3.5 mA
< 3.5 mA
Power factor
> 0.99
> 0.99
> 0.99
> 0.99
> 0.99
DC Output
Max. output voltage U
Max
200 V
360 V
500 V
750 V
1500 V
Max. output current I
Max
210 A
120 A
90 A
60 A
30 A
Max. output power P
Max
15 kW
15 kW
15 kW
15 kW
15 kW
Overvoltage protection range
0...220 V
0...396 V
0...550 V
0...825 V
0...1650 V
Overcurrent protection range
0...231 A
0...132 A
0...99 A
0...66 A
0...33 A
Overpower protection range
0…16.50 kW
0…16.50 kW
0…16.50 kW
0…16.50 kW
0…16.50 kW
Temperature coefficient for set
values Δ/K
Voltage / current: 100 ppm
Voltage regulation
Adjustment range
0...200 V
0...360 V
0...500 V
0...750 V
0...1500 V
Accuracy
(1
(at 23 ± 5°C)
< 0.1% U
Max
< 0.1% U
Max
< 0.1% U
Max
< 0.1% U
Max
< 0.1% U
Max
Stability at ±10% ΔU
AC
< 0.02% U
Max
< 0.02% U
Max
< 0.02% U
Max
< 0.02% U
Max
< 0.02% U
Max
Stability at 0...100% load
< 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
< 0.05% U
Max
Rise time 10...90% ΔU
Max. 15 ms
Max. 15 ms
Max. 15 ms
Max. 15 ms
Max. 15 ms
Display: Resolution
See section
„1.9.6.4. Resolution of the displayed values“
Display: Accuracy
(4
≤ 0.2% U
Max
≤ 0.2% U
Max
≤ 0.2% U
Max
≤ 0.2% U
Max
≤ 0.2% U
Max
Ripple
(2
< 300 mV
PP
< 40 mV
RMS
< 320 mV
PP
< 55 mV
RMS
< 350 mV
PP
< 70 mV
RMS
< 800 mV
PP
< 200 mV
RMS
< 2400 mV
PP
< 400 mV
RMS
Remote sensing compensation
Max. 5% U
Max
Max. 5% U
Max
Max. 5% U
Max
Max. 5% U
Max
Max. 5% U
Max
Fall time at no load after switching
DC output off
Down from 100% to <60 V: less than 10 s
Current regulation
Adjustment range
0...210 A
0...120 A
0...90 A
0...60 A
0...30 A
Accuracy
(1
(at 23 ± 5°C)
< 0.2% I
Max
< 0.2% I
Max
< 0.2% I
Max
< 0.2% I
Max
< 0.2% I
Max
Stability at ±10% ΔU
AC
< 0.05% I
Max
< 0.05% I
Max
< 0.05% I
Max
< 0.05% I
Max
< 0.05% I
Max
Stability at 0...100% ΔU
OUT
< 0.15% I
Max
< 0.15% I
Max
< 0.15% I
Max
< 0.15% I
Max
< 0.15% I
Max
Ripple
(2
< 66 mA
RMS
< 50 mA
RMS
< 48 mA
RMS
< 48 mA
RMS
< 26 mA
RMS
Display: Resolution
See section
„1.9.6.4. Resolution of the displayed values“
Display: Accuracy
(4
≤ 0.2% I
Max
≤ 0.2% I
Max
≤ 0.2% I
Max
≤ 0.2% I
Max
≤ 0.2% I
Max
Compensation 10%->90% load
< 2 ms
< 2 ms
< 2 ms
< 2 ms
< 2 ms
Power regulation
Adjustment range
0…15.00 kW
0…15.00 kW
0…15.00 kW
0…15.00 kW
0…15.00 kW
Accuracy
(1
(at 23 ± 5°C)
< 1% P
Max
< 1.2% P
Max
< 1.2% P
Max
< 1.2% P
Max
< 1.2% P
Max
Stability at ±10% ΔU
AC
< 0.05% P
Max
< 0.05% P
Max
< 0.05% P
Max
< 0.05% P
Max
< 0.05% P
Max
Stability at 10-90% ΔU
OUT
* ΔI
OUT
< 0.75% P
Max
< 0.75% P
Max
< 0.75% P
Max
< 0.75% P
Max
< 0.75% P
Max
Display: Resolution
See section
„1.9.6.4. Resolution of the displayed values“
Display: Accuracy
(4
≤ 0.8% P
Max
≤ 0.85% P
Max
≤ 0.85% P
Max
≤ 0.85% P
Max
≤ 0.85% P
Max
Efficiency
(3
~ 95%
~ 94%
~ 95%
~ 94%
~ 95%
(1 Related to the nominal values, the accuracy defines the maximum deviation between an adjusted values and the true (actual) value.
Example: a 80 V model has min. 0.1% voltage accuracy, that is 80 mV. When adjusting the voltage to 5 V, the actual value is allowed to differ max. 80 mV, which
means it might be between 4.92 V and 5.08 V.
(2 RMS value: LF 0...300 kHz, PP value: HF 0...20MHz
(3 Typical value at 100% output voltage and 100% power
(4 The display error adds to the error of the related actual value on the DC output.