Page 45
EPS Stromversorgung GmbH
Alter Postweg 101 • 86159 Augsburg
Germany
Fon: +49 821 / 570451-0
Fax: +49 821 / 570451-25
PSI 9000 3U Series
IF Level 1
Description
Profibus DP
Node Address
Selection of the Profibus or node address of the device within range 1...125 via
direct input
Function Tag
String input box for a user-definable text which describes the Profibus slave function
tag. Max. length: 32 characters
Location Tag
String input box for a user-definable text which describes the Profibus slave location
tag. Max. length: 22 characters
Installation Date
String input box for a user-definable text which describes the Profibus slave instal
-
lation date tag. Max. length: 40 characters
Description
String input box for a user-definable text which describes the Profibus slave.
Max. length: 54 characters
IF Level 1
Description
RS232
-
The baud rate is selectable, other serial settings can’t be changed and are defined
like this: 8 data bits, 1 stop bit, parity = none
Baud rates: 2400, 4800, 9600, 19200, 38400, 57600, 115200
IF Level 1
Level 2
Level 3 Description
Profinet/IO, 1 & 2 Port
IP Settings
DHCP
The IF allows a DHCP server to allocate an IP address, a subnet
mask and a gateway. If no DHCP server is in the network then net
-
work parameters will be set as defined in point “Manual”
Manual
IP
This option is activated by default. An IP address can be maually
allocated.
Gateway
Here a gateway address can be allocated if required..
Subnet
Here a subnet mask can be defined if the default subnet mask is
not suitable.
DNS 1
Here the addresses of the first and second Domain Name Servers
(DNS) can be defined, if needed. A DNS is only necessary if the
device has Internet access and should call Internet URLs, e.g. an
internal eMail system, in order to send an eMail.
DNS 2
Port
Range: 0...65535. Default ports:
5025 = Modbus RTU (for Modbus & SCPI)
Host name
Free choice of host name (default: Client)
Domain name
Free choice of Domain (default: Workgroup)
SMTP
Settings
Server IP
Mail server address, used to send eMails via this mail server, in
order to e.g. report an alarm.
Username
Login to Mailserver, Username
Password
Login to Mailserver, Password
Function Tag
String input box for a user-definable text which describes the Profinet slave function tag.
Max. length: 32 characters
Location Tag
String input box for a user-definable text which describes the Profinet slave location tag.
Max. length: 22 characters
Station Name
String input box for a user-definable text which describes the Profinet station name.
Max. length: 54 characters
Description
String input box for a user-definable text which describes the Profibus slave.
Max. length: 54 characters
Installation Date
String input box for a user-definable text which describes the Profibus slave installation
date tag. Max. length: 40 characters
IF Level 1
Description
Devicenet
Node Address
Selection of the Devicenet node address in the range 0...63
Baud Rate
Selection of the data communication speed with 125 kbps, 250 kbps or 500 kbps (1 kbps
= 1024 Baud) as bus baud rate. Selection „AUTO“ will let the slave device wait for the
master to initiate bus traffic in order to detect the baud rate on the bus automatically