2. Installation
2.7.2 Specifications
Part Number
applicom PCI-DVNIO / PCU-DVNIO
Modes Master/Slave
Baud rates
125, 250, 500 kbps
Interface
1 DeviceNet port
Supported Devices
Group 2 Only Server and U.C.M.M. capable
Maximum Nodes
63
Connection Types
Strobe, Polling, Cyclic and Change of State
Explicit Messaging
Yes
EDS Support
Yes
Input Data Size
1 to 255 bytes
Output Data Size
1 to 255 bytes
Automatic Detection
Yes. Devices can be detected automatically.
2.7.3 Software Installation
Before installing any boards in your controller, you must install the applicomIO console
application and drivers for the type of board you will be using.
(1) Start the controller.
(2) Run the C:\Install\FieldBus\Install\applicomIO\Disk1\Setup.EXE from the install
folder in the controller to start the installation.
(3) Select the desired language for the installer.
(4) Select Install Products.
(5) Select applicomIO. Do not select applicomIO ActiveX.
Fieldbus I/O Rev.6