Maintenance 5. Firmware Update
RC90 (EPSON RC+ 7.0) Rev.8
93
5.3 Controller Recovery
If the Controller becomes inoperable, use the procedures described in this section to
recover.
Controller Backup is recommended for easy recovery of the Controller operation. For
details of Controller Backup, refer to
Maintenance 4. Backup and Restore
.
The following two conditions describe the Controller error status after turning on
the Controller.
Condition A
The Controller automatically changes to Recovery mode and the LED of
ERROR, TEACH, and PROGRAM are lighting. You are able to
communicate with the development PC though the Controller does not
operate properly.
Condition B
The LED of TEACH, AUTO, and PROGRAM do not blink.
Cannot communicate with the Controller using the development PC.
Countermeasure for the error status is as follows.
Condition A
Follow the Firmware Initialization Procedure in
Maintenance
5.4
Firmware Initialization Procedure
Condition B
Execute the following steps:
(1)
Turn OFF the Controller.
(2)
Push the trigger button located on the front side of the Controller and
while holding the button in, turn ON the Controller. Continue to
hold in the trigger button for 30 seconds. This will cause the
Controller to start in Recovery mode.
(3)
Make sure that the LED of ERROR, TEACH, and PROGRAM are
lighting.
(4)
Follow the procedure in
Maintenance 5.4 Firmware Initialization
Procedure
from step (3) to initialize the firmware.
NOTE
Summary of Contents for RC90
Page 1: ...Rev 8 EM158C3031F ROBOT CONTROLLER RC90 EPSON RC 7 0 ...
Page 2: ...ii ROBOT CONTROLLER RC90 EPSON RC 7 0 Rev 8 ...
Page 10: ...viii RC90 EPSON RC 7 0 Rev 8 ...
Page 17: ...Safety This section contains information for safety of the Robot System ...
Page 18: ......
Page 24: ......
Page 28: ...Setup Operation 1 Specifications 12 RC90 EPSON RC 7 0 Rev 8 1 3 Outer Dimensions Unit mm ...
Page 95: ...Maintenance This section contains maintenance procedures for the Robot Controller ...
Page 96: ......