Maintenance 9. Troubleshooting
RC90 (EPSON RC+ 7.0) Rev.8
176
No.
Message
Remedy
Note 1
Note 2
4405
The conveyor is not correctly
initialized.
Rebuild the project.
Delete the conveyor and then reestablish
the setting.
4406
The specified queue data is outside
the set area.
The queue outside of the range cannot be
tracked. If the specified queue is above
the upstream limit, change the program
so that tracking does not start until the
queue enters the area below the upper
limit. If the specified queue is below
the downstream limit, change the
program to delete the queue data.
4407
The encoder is not correctly assigned.
Set the encoder.
4409
The parameter of the conveyor
instruction is invalid.
Review the parameter.
4410
A conveyor coordinates conversion
error occurred.
Rebuild the project.
Delete the conveyor and then reestablish
the setting.
4411
Communication error within the
Conveyor Modules.
Reboot the controller.
Initialize the controller firmware.
Replace the controller.
4413
Conveyor tracking starting error.
Reboot the controller.
Initialize the controller firmware.
Replace the controller.
4414
Conveyor tracking cannot start after
motion with CP ON.
Start the conveyor tracking using
CP OFF.
4415
The setting of Diagonal Upstream
Limit or Diagonal Downstream Limit
is not appropriate.
The diagonal downstream limit is above
the upstream limit, or the diagonal
upstream/downstream limit is horizontal
to the conveyor direction. Review the
setting of diagonal upstream/downstream
limit.
Summary of Contents for RC90
Page 1: ...Rev 8 EM158C3031F ROBOT CONTROLLER RC90 EPSON RC 7 0 ...
Page 2: ...ii ROBOT CONTROLLER RC90 EPSON RC 7 0 Rev 8 ...
Page 10: ...viii RC90 EPSON RC 7 0 Rev 8 ...
Page 17: ...Safety This section contains information for safety of the Robot System ...
Page 18: ......
Page 24: ......
Page 28: ...Setup Operation 1 Specifications 12 RC90 EPSON RC 7 0 Rev 8 1 3 Outer Dimensions Unit mm ...
Page 95: ...Maintenance This section contains maintenance procedures for the Robot Controller ...
Page 96: ......