8.2.4 Inputs/Output
By default, the GenLoc 41e provides 3 opto-coupled inputs (I1 to I3) and 1 open-collector output (O1).
As an option, it is possible to have an analog input instead of the opto-coupled input I2.
8.2.4.1 Opto-coupled Inputs (I1, I2, I3)
Table: Diode Characteristics of the opto-coupled inputs
Characteristics
Symbols
Conditions
Min.
Typ.
Max.
Unit
max. current
I
F (rms)
50
mA
max. inverted voltage
V
R
5
V
Direct voltage
V
F
I
F
= 10 mA
1.0
1.15
1.3
V
Inverted current
I
R
V
R
= 5 V
10
µA
Capacity
C
T
V=0, f = 1 MHz
---
30
---
pF
Transfer Ratio
I
C
/ I
F
I
F
= 5 mA, V
CE
= 5 V
50
---
600
%
Saturation of the transfer ratio
I
C
/ I
F (SAT)
I
F
= 1 mA, V
CE
= 0.4 V
60
%
Command voltage
3,5
35
V
Idle voltages
1
V
Internal electric scheme of the 3 inputs
The minimum of voltage command for detection is: 3.5
V
The maximum voltage command is:
35 V