background image

 

 

DINLINE ALARM RELAY

 

 

INSTALLATION INSTRUCTIONS

 

 

www.erico.com 

Page 2 of 2 

Doc: HBCR1681,  Rev: 1  

 

5.  INTERCONNECTION 

When connecting the DAR to a single opto-coupler output the 

+ terminal of the SPD should connect to the + terminal on the 

DAR. The – terminal should connect to the -- terminal. 

 

To transient

protected

equipment

To remote alarm circuit

DSD 2S/2T

N E

Ph

DAR

N

Ph

Voltage free contacts

Opto-coupler output

 

+/- terminal connections are polarity sensitive. Do not reverse. 
 
When connecting the DAR to multiple opto-couplers the opto-

couplers should be connected in series with + terminal of one 

connected to the  – terminal of the next. The DAR + terminal 

should  connect  to  +  SPD  terminal  at  one  end  of  the  series 

connection  and  the  –  DAR  terminal  connect  to  the  – SPD 

terminal at the other end of the series connection. 

 

DSD 2S/2T

Up to 16 connections per DAR module

N

E

Ph

N E

Ph

DAR

N

Ph

Voltage free contacts

 

+/- terminal connections are polarity sensitive. Do not reverse. 
 

5.  STATUS INDICATION 

Normal(green) indicator OFF

Red indicator ON

Relay is de-energised

Power is supplied

Normal(green) indicatorOFF

Red indicator OFF

Relay is de-energised

Power is OFF

Normal

4

Fault

6

8

Normal

4

Fault

6

8

DSDin alarm mode or power

to DSD has been removed

Power to DAR removed

Protection status unknown

DISPLAY

EXPLANATION

Normal

Fault

6

4

8

Normal(green) indicator ON

Red indicator OFF

Relay is energised

Power is supplied

Normal operation

Protection Operational

STATUS

Protection Alarm

Fault Mode

 

 

6.  FUSING AND ISOLATION 

Overcurrent protection must be installed in the upstream circuit 

of the power supply to the DAR to provide protection to the 

unit itself and the wiring in case of fault conditions. 
The  fuse  rating  should  be  based  on  the  wiring  size  used  to 

connect to the DAR Ph & N terminals. Australian regulations 

AS3000-1991,  Table  B2  specifies  the  following  upstream 

protection for single phase circuits, unenclosed in air. 
 

Cable Size  

HRC Fuse or  

CB Rewirable Fuse 

1.5mm

2

  

 

16A  

 

12A 

2.5mm

2

  

 

20A  

 

16A 

4mm

2

  

 

25A  

 

20A 

6mm

2

  

 

32A  

 

25A 

 
Where  overcurrent  protection  of  the  appropriate  rating  or 

smaller  is  already  fitted  in  the  upstream  circuit,  overcurrent 

protection at the DAR will not be required 

6.  MAINTENANCE & TESTING

 

Before  removing  a  DAR  unit  from  service,  ensure  that  the 

power  has  been  removed.  Maintenance,  testing  and 

replacement should only be undertaken by qualified personnel. 
Testing of a DAR unit which is connected to a fully functional 

DSD unit can be accomplished by removing power to the DSD 

only.  The  DAR  Status  indication  and  output  contacts  should 

alter from the Normal to Fault condition.  
Testing  of  the  DAR  unit  alone  may  be  accomplished  by 

disconnecting the + /  -connections to the unit. When power is 

applied the DAR “Fault” Status Indicator should be illuminated. 

By connecting the + / - terminals together, the “Normal” Status 

Indicator  should  be  illuminated.  The  output  contacts  should 

alter to the appropriate state.  

7.  USE OF OTHER INTERFACES

 

Only  DAR  units  are  recommended  for  the  interfacing  of 

equipment to the DSD, TDS & TDF opto-coupler alarm output 

circuit(s). The  direct connection of other equipment to these 

opto-coupler alarm outputs may not provide sufficient isolation 

or exceed the opto-coupler specifications. This may damage 

the  SPD  and/or  the  connected  equipment.  Warranty  may  be 

voided under such circumstances.  

NOTE:

 In connecting to the SPD opto-coupler alarm 

output(s), do not reverse the +/- connections as 
damage may occur

LN

E

( 4 - 6 m m )

B u n d l e / t w i s t

t o g e t h e r

S

u

p

p

l

y

Keep 

as 

 

shor

a s  p r a c t i c a l

S e e  

s e c t i o n  

8

f o r  f u s i n g  d e t a i l s

N

L

 

PRV Switchboard Manual Section 2 - Terasaki Circuit Breakers Installation Instructions Vendor Manual

Q-Pulse Id: VM78

12/11/2012

Page 2 of 2

Reviews: