Site Preparation
Caution!
Risk of equipment damage. The SmartEdge 600 router can be damaged by
lack of proper cooling and ventilation. To reduce the risk, never install the
chassis in an unventilated area, and always ensure that cooling equipment
sufficient to maintain a temperature of less than 104
F (40
C) is available.
Table 6
Environmental Requirements
Specification
Value
Cooling
Forced air (fan cooled)
Operating temperature, nominal
41
to 104
F (5
to 40
C)
Operating temperature, short term
(1)
23
to 131
F (–5
to 55
C)
Storage temperature
-38
to 150
F (–40
to 70
C)
Operating relative humidity
5 to 95% RH (noncondensing)
Storage relative humidity
5 to 95% RH (noncondensing)
Operating altitude
0 to 10,000 ft (3,048m)
Earthquake
Telcordia 63-CORE Zone 4-compliant
Thermal dissipation, maximum
2,736 watts (9,336 BTU/hour)
(1) Short term refers to a period of time not more than 96 consecutive hours and a total of not more than 15 days in
one year (360 hours in any given year, but no more than 15 occurrences during that year).
1.5
Physical Specifications
Figure 1
SmartEdge 600 Chassis Dimensions
Chassis depth dimension includes the front cable tray and the power safety
cover.
5
27/153 30-CRA 119 1170/1 Uen A
|
2010-04-09
Summary of Contents for SmartEdge 600
Page 1: ...SmartEdge 600 Router Hardware Guide Release 6 3 INSTALLATION 27 153 30 CRA 119 1170 1 Uen A ...
Page 6: ...SmartEdge 600 Router Hardware Guide 27 153 30 CRA 119 1170 1 Uen A 2010 04 09 ...
Page 26: ...SmartEdge 600 Router Hardware Guide 20 27 153 30 CRA 119 1170 1 Uen A 2010 04 09 ...
Page 108: ...SmartEdge 600 Router Hardware Guide 102 27 153 30 CRA 119 1170 1 Uen A 2010 04 09 ...
Page 112: ...SmartEdge 600 Router Hardware Guide 106 27 153 30 CRA 119 1170 1 Uen A 2010 04 09 ...