6 Offliner Settings Software
6-18
L-PRO 4000 User Manual
D02706R02.30
Class data for each DNP point can be assigned on the Class Data screen. Only
Points which were mapped in the Point Map screen will appear here. Sections
for Binary Inputs and Analog Inputs appear here; Binary Outputs cannot be as-
signed a Class. The list is scrollable by using the scroll control on the right hand
side.
In addition to assigning a Change Event Class to each mapped point, most An-
alog Inputs can also be assigned a Deadband and Scaling factor.
SCADA
Settings
Summary
Figure 6.15: SCADA Settings Summary
This screen provides a summary of the current SCADA settings as set in the
working setting file. This includes SCADA Communication parameters and (if
the SCADA mode is set to DNP) Binary Input, Binary Output, and Analog In-
put information including Deadband and Scaling factors.
This SCADA Summary screen is scrollable and can be printed.