6 Offliner Settings Software
D02706R02.30
L-PRO 4000 User Manual
6-19
Record Length
Figure 6.16: Record Length
The relay has recording and logging functions to analyze faults and dynamic
swing, and to review the operation of the overall protection scheme.
This screen displays the record length for each of the two types of recordings
provided: fault and swing. Pre-trigger times are configurable between 0.10 to
2.00 seconds for fault records and fixed at 30 seconds for swing records and
are included as part of the record length.
Table 6.10: Record Length
Fault
Fault Record Length
0.2 to 10.0 seconds
Prefault Time
0.10 to 2.00 seconds
Swing
Swing Record Length
60 to 120 seconds
Event Auto Save
Enable/Disable