6 Offliner Settings Software
6-20
L-PRO 4000 User Manual
D02706R02.30
Setting Groups
Figure 6.17: Setting Groups Comments
The relay has 8 setting groups (SG). The user can change all relay setting pa-
rameters except the physical connections such as input or output parameters in
each setting group. Use any one of the 16 available Group Logic Statements
per setting group to perform Setting Group changes. The Group Logic state-
ments are similar to the ProLogic statements with the following exceptions, the
sole function is to activate one of the 8 setting groups and the processing is in
a slower half second cycle. Group Logic inputs statements can be driven from
ProLogic or any external input or virtual input or from previous Group Logic
statements. Each Group Logic statement includes 5 inputs (with Boolean state-
ments), one latch state and one pickup delay timer. View the active setting
group (ASG) from the Terminal Mode, from the front panel or from a record
stored by the relay (the active setting group is stored with the record).