Figure 7.40: Using Virtual Input to simulate SCADA Recloser Lockout Reset
ProLogic 7: This equation is intended only for giving indication of when the
79 Lockout is reset.
This indication, along with ProLogic 6, proves the 79 Reset timer (TD).
Figure 7.41: Main Recloser Lockout Reset Indication
ProLogic 8: This equation closes Out 6 to simulate auxiliary breaker closed
status from SCADA breaker close command OR auxiliary recloser operation.
This latching function resets when an external trip is received.