Appendix B IED Settings and Ranges
D02706R02.30
L-PRO 4000 User Manual
Appendix B-5
KM1 Angle
0
deg
-25.0 to 25.0
KM2 Mutual Line 2
Enabled
KM2 Magnitude
1
-
0.10 to 2.00
KM2 Angle
0
deg
-25.0 to 25.0
Scheme Selector
Distance Scheme selection
Basic
Basic/POTT/PUTT/DCB
Protection Scheme
3 Phase
3 Phase/1 Phase/1 or 3
Phase
1Ph Max Open Pickup Delay (TM)
2.5
s
0.100 to 5.000
1Ph/3Ph for 3Ph Dropout Delay (TD4)
25.000 seconds
s
0.100 to 999.000
1Ph/3Ph for 1Ph Pickup Delay (TL5)
0.100 seconds
s
0.100 to 5.000
1Ph/3Ph for 1Ph Dropout Delay (TD5)
25.000 seconds
s
0.100 to 999.000
Communication Receiver1
EI 1 [EI Spare 1]
Communication Receiver2
<disabled>
Scheme Send Pickup Delay (TL3)
00.000 seconds
s
0.000 to 1.000
Scheme Send Dropout Delay (TD3)
0.100 seconds
s
0.000 to 1.000
POTT Current Reversal Pickup Delay (TL1)
0.000 seconds
s
0.000 to 0.500
POTT Current Reversal Dropout Delay (TD1)
0.100 seconds
s
0.000 to 0.500
DCB Scheme Zone 2 Pickup Delay (TL2)
0.050 seconds
s
0.005 to 0.500
DCB Scheme Receiver Dropout Delay (TD2)
0.100 seconds
s
0.000 to 0.500
DEF Scheme Selection
Disabled
Communication Receiver3
<disabled>
DEF Scheme Send Pickup Delay (TL6)
0.1
s
0.000 to 1.000
DEF Scheme Send Dropout Delay (TD6)
0.2
s
0.000 to 1.000
External Single Phase Receiver1
<disabled>
External Single Phase Receiver2
<disabled>
External Single Phase Receiver3
<disabled>
External Single Phase Receiver4
<disabled>
External Single Phase Receiver5
<disabled>
External Single Phase Receiver6
<disabled>
50N-67F - Overcurrent Carrier Start
Action
<diabled>
Direction
Forward
3I0 Pickup
1
A
0.2 to 50.0
Pickup Delay
0.02
s
0.005 to 99.99 seconds
50N-67R - Overcurrent Carrier Block
Action
<diabled>
Direction
Reverse
3I0 Pickup
1
A
0.2 to 50.0
Pickup Delay
0.02
s
0.005 to 99.99 seconds
52 - Breaker Status
Summary of Contents for L-PRO 4000
Page 1: ...L PRO 4000 Transmission Line Protection Relay User Manual Version 2 3 Rev 0...
Page 2: ......
Page 4: ......
Page 8: ......
Page 10: ......
Page 14: ......
Page 40: ......
Page 50: ......
Page 116: ......
Page 146: ......
Page 218: ......
Page 252: ...Appendix B IED Settings and Ranges Appendix B 34 L PRO 4000 User Manual D02706R02 30...
Page 260: ......
Page 270: ......
Page 302: ......
Page 308: ......
Page 310: ......
Page 312: ......