Appendix B IED Settings and Ranges
Appendix B-8
L-PRO 4000 User Manual
D02706R02.30
Type
Quadrilateral
Forward Reach
15.00
0.00 to 66.00
Reverse Reach
0.00
0.00 to 66.00
Left Reach (R1)
15.00
0.05 to 66.00
Right Reach (R2)
15.00
0.05 to 66.00
Mho Char. Angle
90.0
70.0 to 140.0
Pickup Delay
1.5
0.00 to 99.99
Phase Current Supervision
1.0
0.2 to 50.0
3I0 Supervision
1.0
0.2 to 50.0
21N, Zone 4
Disabled
Type
Quadrilateral
Forward Reach
0.00
0.00 to 66.00
Reverse Reach
2.00
0.00 to 66.00
Left Reach (R1)
5.00
0.05 to 66.00
Right Reach (R2)
5.00
0.05 to 66.00
Mho Char. Angle
90.0
70.0 to 140.0
Pickup Delay
1.5
0.00 to 99.99
Phase Current Supervision
1.0
0.2 to 50.0
3I0 Supervision
1.0
0.2 to 50.0
21N, Zone 5
Disabled
Type
Quadrilateral
Forward Reach
20.00
0.00 to 66.00
Reverse Reach
5.00
0.00 to 66.00
Left Reach (R1)
15.00
0.05 to 66.00
Right Reach (R2)
15.00
0.05 to 66.00
Mho Char. Angle
90.0
70.0 to 140.0
Pickup Delay
1.5
0.00 to 99.99
Phase Current Supervision
1.0
0.2 to 50.0
3I0 Supervision
1.0
0.2 to 50.0
68 Off
Power Swing Block/Trip
Power swing timer
0.05
3I0 Blocking
2.5 A
Blocking Reset Time
2.00 s
LHS Outer (R1)
27.0
LHS Inner (R2)
18.0
RHS Inner (R3)
18.0
RHS Outer (R4)
27.0
Top Outer (X4)
27.0
Top Inner (X2)
18.0
Summary of Contents for L-PRO 4000
Page 1: ...L PRO 4000 Transmission Line Protection Relay User Manual Version 2 3 Rev 0...
Page 2: ......
Page 4: ......
Page 8: ......
Page 10: ......
Page 14: ......
Page 40: ......
Page 50: ......
Page 116: ......
Page 146: ......
Page 218: ......
Page 252: ...Appendix B IED Settings and Ranges Appendix B 34 L PRO 4000 User Manual D02706R02 30...
Page 260: ......
Page 270: ......
Page 302: ......
Page 308: ......
Page 310: ......
Page 312: ......