Appendix B IED Settings and Ranges
D02706R02.30
L-PRO 4000 User Manual
Appendix B-9
Bottom Inner (X2)
18.0
Bottom Outer (X1)
27.0
Switch-On-To-Fault (SOTF)
Disabled
Breaker Signal
Close Command
Close Pulse
EI 1 [EI Spare 1]
Pole Dead Pickup
0.2 s
Main Breaker
EI 1 [EI Spare 1]
Aux Breaker
<disabled>
Enable Duration
0.2 s
50 Pickup
2.5 A
50N Pickup
2.5 A
I2/I1 Pickup
0.2
Weak Infeed
Disabled
27V1 Pickup
51.0 V
59 3V0
5.0 V
25 Sync Check
Disabled
Frequency difference
Disabled
Frequency difference
0.01 Hz
0.010 to 2.000 Hz
Dead Main Live Aux (DMLA)
Disabled
Live Main Dead Aux (LMDA)
Disabled
Dead Main Dead Aux (DMDA)
Disabled
79-3Ph Recloser
Disabled
Initiate Reset (TDI)
0.1
Block Reset (TDB)
0.1
79-1Ph Recloser
Disabled
Initiate Reset (TDI)
0.1
Block Reset (TDB)
0.1
59 Main
Disabled
Default Gate
OR
Default pickup value
5.0 s
Gate switch option
AND/OR
59 Aux
Disabled
Default Gate
OR
Default pickup value
5.0 s
Gate switch option
AND/OR
59N Definite Time Delay
Disabled
59N Inverse Time Delay
Disabled
27 Main
Disabled
Default pickup value
25.0 V
Pickup delay
5,00 s
Summary of Contents for L-PRO 4000
Page 1: ...L PRO 4000 Transmission Line Protection Relay User Manual Version 2 3 Rev 0...
Page 2: ......
Page 4: ......
Page 8: ......
Page 10: ......
Page 14: ......
Page 40: ......
Page 50: ......
Page 116: ......
Page 146: ......
Page 218: ......
Page 252: ...Appendix B IED Settings and Ranges Appendix B 34 L PRO 4000 User Manual D02706R02 30...
Page 260: ......
Page 270: ......
Page 302: ......
Page 308: ......
Page 310: ......
Page 312: ......