Appendix B IED Settings and Ranges
D02706R02.30
L-PRO 4000 User Manual
Appendix B-11
46-50
Disabled
46-51
Disabled
21P - Phase Distance: Zone 1
21P - Zone 1
Disabled
Type
Quadrilateral
Forward Reach
8
ohm
0.00 to 66.00
Left Reach (R1)
10
ohm
0.05 to 66.00
Right Reach (R2)
10
ohm
0.05 to 66.00
Mho Char. Angle
90
deg
70.0 to 140.0
Pickup Delay
0
s
0.00 to 99.99
Delta Current Supervision
0.2
A
0.2 to 50.0
21P - Phase Distance: Zone 2
21P - Zone 2
Disabled
Type
Quadrilateral
Forward Reach
12
ohm
0.00 to 66.00
Left Reach (R1)
15
ohm
0.05 to 66.00
Right Reach (R2)
15
ohm
0.05 to 66.00
Mho Char. Angle
90
deg
70.0 to 140.0
Pickup Delay
0.5
s
0.00 to 99.99
Delta Current Supervision
0.2
A
0.2 to 50.0
21P - Phase Distance: Zone 3
21P - Zone 3
Disabled
Type
Quadrilateral
Forward Reach
15
ohm
0.00 to 66.00
Reverse Reach
0
ohm
0.00 to 66.00
Left Reach (R1)
15
ohm
0.05 to 66.00
Right Reach (R2)
15
ohm
0.05 to 66.00
Mho Char. Angle
90
deg
70.0 to 140.0
Pickup Delay
1.5
s
0.00 to 99.99
Delta Current Supervision
0.2
A
0.2 to 50.0
21P - Phase Distance: Zone 4
21P - Zone 4
Disabled
Type
Quadrilateral
Forward Reach
0
ohm
0.00 to 66.00
Reverse Reach
2
ohm
0.00 to 66.00
Left Reach (R1)
5
ohm
0.05 to 66.00
Right Reach (R2)
5
ohm
0.05 to 66.00
Mho Char. Angle
90
deg
70.0 to 140.0
Pickup Delay
1.5
s
0.00 to 99.99
Delta Current Supervision
0.2
A
0.2 to 50.0
Summary of Contents for L-PRO 4000
Page 1: ...L PRO 4000 Transmission Line Protection Relay User Manual Version 2 3 Rev 0...
Page 2: ......
Page 4: ......
Page 8: ......
Page 10: ......
Page 14: ......
Page 40: ......
Page 50: ......
Page 116: ......
Page 146: ......
Page 218: ......
Page 252: ...Appendix B IED Settings and Ranges Appendix B 34 L PRO 4000 User Manual D02706R02 30...
Page 260: ......
Page 270: ......
Page 302: ......
Page 308: ......
Page 310: ......
Page 312: ......