Appendix B IED Settings and Ranges
Appendix B-14
L-PRO 4000 User Manual
D02706R02.30
Out of step Swing Timer
0.05
s
0.00 to 1.00
I1 Supervision
10
A
0.5 to 50.0
3Io Blocking
2.5
A
0.5 to 50.0
Blocking Reset Time
2
s
0.25 to 2.00
Top Blinder - Outer (X4)
27
ohm
18.0 to 100.0
Top Blinder - Inner (X3)
18
ohm
-18.0 to 27.0
Bottom Blinder - Inner (X2)
-18
ohm
-27.0 to 18.0
Bottom Blinder - Outer (X1)
-27
ohm
-100.0 to -18.0
LHS Blinder - Outer (R1)
-27
ohm
-100.0 to -18.0
LHS Blinder - Inner (R2)
-18
ohm
-27.0 to 18.0
RHS Blinder - Inner(R3)
18
ohm
-18.0 to 27.0
RHS Blinder - Outer(R4)
27
ohm
18.0 to 100.0
Switch-On-To-Fault (SOTF)
Disabled
Enable Duration
0.2
s
0.0 to 999.9
Breaker Signal
Close Command
Close Pulse
EI 1 [EI Spare 1]
Pole Dead Pickup
0.2
s
0.0 to 999.9
Main Breaker
EI 1 [EI Spare 1]
Aux Breaker
<disabled>
Enable Duration
0.2 s
s
0.0 to 999.9
50 Pickup
2.5
A
0.5 to 50.0
50N Pickup
2.5
A
0.5 to 50.0
I2/I1 Pickup
0.2
-
0.0 to 10.0
Weak Infeed
Disabled
27 V1 Pickup
51
V
0.0 to 69.0
59 3V0 Pickup
5
V
0.0 to 100.0
Zone2/Zone4 Reset Delay (TWD1)
0.1
s
0.02 to 0.20
Comm. Cycle Reset Delay (TWD2)
0.05
s
0.02 to 0.20
Comm. Reset Time Delay (TWD3)
0.15
s
0.02 to 1.00
25/27/59 - Sync Check
25 Sync Check
Disabled
Maximum Voltage
70
V
60.0 to 138.0
Minimum Voltage
40
V
40.0 to 69.9
Angle Difference
20
deg
1.0 to 50.0
Pickup Delay
0.1
s
0.00 to 10.00
Frequency Difference
Disabled
Frequency Difference
0
Hz
0.010 to 2.000
Dead Main Live Aux. (DMLA)
Disabled
Live Main Dead Aux. (LMDA)
Disabled
Dead Main Dead Aux. (DMDA)
Disabled
Summary of Contents for L-PRO 4000
Page 1: ...L PRO 4000 Transmission Line Protection Relay User Manual Version 2 3 Rev 0...
Page 2: ......
Page 4: ......
Page 8: ......
Page 10: ......
Page 14: ......
Page 40: ......
Page 50: ......
Page 116: ......
Page 146: ......
Page 218: ......
Page 252: ...Appendix B IED Settings and Ranges Appendix B 34 L PRO 4000 User Manual D02706R02 30...
Page 260: ......
Page 270: ......
Page 302: ......
Page 308: ......
Page 310: ......
Page 312: ......