Appendix F DNP3 Device Profile
D02706R02.30
L-PRO 4000 User Manual
Appendix F-29
Implementation
Table
The following implementation table identifies which object groups and varia-
tions, function codes and qualifiers the device supports in both requests and re-
sponses. The Request columns identify all requests that may be sent by a
Master, or all requests that must be parsed by an Outstation. The Response col-
umns identify all responses that must be parsed by a Master, or all responses
that may be sent by an Outstation.
NOTE
The implementation table must list all functionality required by the device wheth-
er Master or Outstation as defined within the DNP3 IED Conformance Test Pro-
cedures. Any functionality beyond the highest subset level supported is
indicated by highlighted rows. Any Object Groups not provided by an outstation
or not processed by a Master are indicated by strikethrough (note these Object
Groups will still be parsed).
DNP Object Group & Variation
Request
Outstation parses
Response
Outstation can issue
Group
Num
Var
Num
Description
Function Codes
(dec)
Qualifier Codes (hex)
Function Codes
(dec)
Qualifier Codes (hex)
1
0
Binary Input - Any Variation
1 (read)
06 (no range, or all)
129 (response)
00, 01 (start-stop)
00, 01 (start-stop)
07, 08 (limited qty)
17, 28 (index)
1
1
Binary Input - Packed format
1 (read)
06 (no range, or all)
00, 01 (start-stop)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
1
2
Binary Input - With flags
1 (read)
06 (no range, or all)
00, 01 (start-stop)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
2
0
Binary Input Event - Any Variation
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129 (response)
17, 28 (index)
2
1
Binary Input Event - Without time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28 (index)
2
2
Binary Input Event - With absolute
time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28 (index)
2
3
Binary Input Event - With relative
time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28 (index)
10
0
Binary Output - Any Variation
1 (read)
06 (no range, or all)
129 (response)
00, 01 (start-stop)
00, 01 (start-stop)
07, 08 (limited qty)
17, 28 (index)
10
2
Binary Output - Output Status with
flag
1 (read)
06 (no range, or all)
00, 01 (start-stop)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
12
1
Binary Command - Control relay
output block (CROB)
3 (select)
4 (operate)
5 (direct op)
6 (dir. op, no ack)
17, 28 (index)
129 (response)
Echo of request
Summary of Contents for L-PRO 4000
Page 1: ...L PRO 4000 Transmission Line Protection Relay User Manual Version 2 3 Rev 0...
Page 2: ......
Page 4: ......
Page 8: ......
Page 10: ......
Page 14: ......
Page 40: ......
Page 50: ......
Page 116: ......
Page 146: ......
Page 218: ......
Page 252: ...Appendix B IED Settings and Ranges Appendix B 34 L PRO 4000 User Manual D02706R02 30...
Page 260: ......
Page 270: ......
Page 302: ......
Page 308: ......
Page 310: ......
Page 312: ......