Appendix L L-PRO Setting Example
D02706R02.30
L-PRO 4000 User Manual
Appendix L-3
Prologic 10 has no intentional delay and becomes high for the combined drop-
out time of ProLogic 9 and 10 equalling 0.52 seconds.
Figure L.2: ProLogic 10
Group Logic 1 is used to switch to the new setting group; there is no intentional
delay. The user can also provide 4 additional logic inputs to be used to provide
qualifiers before switching setting groups. The example uses a ProLogic state-
ment and an external input as qualifiers, see example “Using ProLogic to Qual-
ify Group Logic Statements” in Appendix L’ on page Appendix L-8.
Figure L.3: Group Logic 1