Appendix L L-PRO Setting Example
D02706R02.30
L-PRO 4000 User Manual
Appendix L-17
8 Go to the Control Virtual Inputs and “close” 52-1 and 52-2 using the Pulse
On action for the Virtual Input 1 and Virtual Input 2. This will activate Pro-
Logic 2 and 4.
Figure L.31: Control Virtual Input '52-1 Close 52-CS' to 'Pulse On'
9 Check the event log for VI1 and VI3 along with PL2 and PL4.
Figure L.32: '52-1 a status: High 'and '52-2 a status: High'