4 Protection Functions and Specifications
D02706R02.30
L-PRO 4000 User Manual
4-7
Upper angle (degrees)
90.1 to 179.9
Both
Lower angle (degrees)
180.1 to 269.9
Both
RHS
Impedance (Ohms sec-
ondary)
0.01 to 66.0 (5 A)
0.05 to 330.0 (1 A)
Both
Upper angle (degrees)
0.1 to 89.9
Both
Lower angle (degrees)
-0.1 to -89.9
Both
Table 4.1: 21P Phase Distance Element Settings
Table 4.2: 21N Ground Distance Element Settings
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Enable/ Disa-
ble
Enable/ Disa-
ble
Enable/ Disa-
ble
Enable/ Disa-
ble
Enable/ Disa-
ble
Characteristic Type
Mho / Quadri-
lateral
Mho / Quadri-
lateral
Mho / Quadri-
lateral
Mho / Quadri-
lateral
Mho / Quadri-
lateral
Forward Impedance
Reach (Ohms secondary)
0.00 to 66.00
(5A)
0.00 to
330.00 (1A)
0.00 to 66.00
(5A)
0.00 to
330.00 (1A)
0.00 to 66.00
(5A)
0.00 to
330.00 (1A)
0.00 to 66.00
(5A)
0.00 to
330.00 (1A)
0.00 to 66.00
(5A)
0.00 to
330.00 (1A)
Both
Forward Reactance
Reach (Ohms secondary)
0.00 to 66.00
(5A)
0.00 to
330.00 (1A)
0.00 to 66.00
(5A)
0.00 to
330.00 (1A)
0.00 to 66.00
(5A)
0.00 to
330.00 (1A)
0.00 to 66.00
(5A)
0.00 to
330.00 (1A)
0.00 to 66.00
(5A)
0.00 to
330.00 (1A)
Quadrilateral
Reverse Impedance
Reach (Ohms secondary)
0.00 to 66.00
(5A)
0.00 to
330.00 (1A)
0.00 to 66.00
(5A)
0.00 to
330.00 (1A)
0.00 to 66.00
(5A)
0.00 to
330.00 (1A)
Both
Reverse Reactance
Reach (Ohms secondary)
0.00 to 66.00
(5A)
0.00 to
330.00 (1A)
0.00 to 66.00
(5A)
0.00 to
330.00 (1A)
0.00 to 66.00
(5A)
0.00 to
330.00 (1A)
Quadrilateral
Left Reach (R1) (Ohms
secondary)
0.05 to 66.00
(5A)
0.25 to
330.00 (1A)
0.05 to 66.00
(5A)
0.25 to
330.00 (1A)
0.05 to 66.00
(5A)
0.25 to
330.00 (1A)
0.05 to 66.00
(5A)
0.25 to
330.00 (1A)
0.05 to 66.00
(5A)
0.25 to
330.00 (1A)
Quadrilateral
Right Reach (R2) (Ohms
secondary)
0.05 to 66.00
(5A)
0.25 to
330.00 (1A)
0.05 to 66.00
(5A)
0.25 to
330.00 (1A)
0.05 to 66.00
(5A)
0.25 to
330.00 (1A)
0.05 to 66.00
(5A)
0.25 to
330.00 (1A)
0.05 to 66.00
(5A)
0.25 to
330.00 (1A)
Quadrilateral
Mho Characteristic Angle
(degrees)
70.0 to 140.0
70.0 to 140.0
70.0 to 140.0
70.0 to 140.0
70.0 to 140.0
Mho
Pickup Delay (seconds)
0.00 to 99.00
0.00 to 99.00
0.00 to 99.00
0.00 to 99.00
0.00 to 99.00
Both
Summary of Contents for L-PRO 4000
Page 1: ...L PRO 4000 Transmission Line Protection Relay User Manual Version 2 3 Rev 0...
Page 2: ......
Page 4: ......
Page 8: ......
Page 10: ......
Page 14: ......
Page 40: ......
Page 50: ......
Page 116: ......
Page 146: ......
Page 218: ......
Page 252: ...Appendix B IED Settings and Ranges Appendix B 34 L PRO 4000 User Manual D02706R02 30...
Page 260: ......
Page 270: ......
Page 302: ......
Page 308: ......
Page 310: ......
Page 312: ......