21
d)
LOWSET - 1 N/O contact
This contact to be used while testing the LOWSET characteristic.
e) PROTECTION HEALTHY - 1 N/C contact
This contact indicates the relay healthiness.
5.3. Primary Injection
Primary injection tests are essential to check the ratio and polarity of the transformers as
well as the secondary wiring.
Ensure the instrument transformer is potential type and isolated from the primary system.
Using the circuit shown in Fig.7, check the current transformer ratio and CT phase to earth
connection. Inject a current of sufficient magnitude .The secondary current is
Is = Primary current / CT ratio
5.4. Putting Into Service
After completing all tests satisfactorily, the relay should be put into service as follows:
Make a final check of the secondary wiring and tightness of all terminal connections.
Insert the DC supply fuse.
Check the relay healthy indication/display.
Replace the relay cover.
Insert the trip links.
Perform trip test by secondary injection.
Remove all test connections