? Error code
C.
and
9
flash alternately and the
light is red?
!
Temperature sensor incorrectly connected.
•
Check contact at connector X22.
!
Temperature sensor is below -30°C.
!
Temperature sensor defective.
•
Replace temperature sensor.
!
Incorrect temperature sensor.
▷
Sensor BCU is not compatible with the ACU.
•
Select the correct temperature sensor for the
ACU.
? Error code
E.
and
1
flash alternately?
!
The remote reset input is defective.
•
If you use the remote reset input, contact your
supplier.
? Error code
E.
and
2
flash alternately and the
light is red?
!
An adjustable parameter and the CRC check are
not the same. The parameters are implausible.
•
Order a new BCC. Contact your supplier.
▷
Reset is only possible by pressing the RESET
button on the burner control unit or using the
remote reset if there is one.
? Error code
E.
and
3
flash alternately and the
light is red?
!
A fixed parameter and the CRC check are not
the same. The parameters are implausible.
•
Order a new BCC. Contact your supplier.
▷
Reset is only possible by pressing the RESET
button on the burner control unit or using the
remote reset if there is one.
? Error code
E.
and
4
flash alternately and the
light is red?
!
Limits for fixed parameters not observed.
•
Order a new BCC. Contact your supplier.
? Error code
E.
and
5
flash alternately and the
light is red?
!
The BCC is not connected.
•
Connect the BCC to the printed circuit board.
? Error code
E.
and
6
flash alternately and the
light is red?
!
An incorrect BCC is connected. The BCC must
be compatible with the GP.
•
Remove the BCC and connect the correct BCC
to the printed circuit board, see page 6 (Burn-
er Chip Card (BCC)).
? Error code
E.
and
8
flash alternately?
!
Programming mode is active.
•
As soon as Programming mode has been de-
activated, the display will go out.
? Error code
E.
and
9
flash alternately?
!
Internal electronics fault.
•
Remove the BCC and return it to the supplier.
? Error code
U.
and
1
flash alternately and the
light is red?
!
Voltage supply is below the limit (programmable
limit, e.g. < 160 V).
•
Ensure that adequate mains voltage is supplied.