GB-23
D
GB
NL
RUS
PL
F
E
UA
CN
Technical data
Gas types: II2ELL3B/P,
natural gas H and L (gases of category 2);
LPG, gaseous (gases of category 3): propane,
propane/butane, butane.
NOx Class: depending on gas type up to Class 5.
Inlet pressure p
u
: 20 to 70 mbar.
Resistant to high-pressure cleaning.
Gas connection: R ¾ to ISO 7-1.
Staged control: On/Off signal (240 V AC or
24 V AC/DC via coupling relay).
Burner control unit with direct spark ignition and
ionization control.
Fan type:
main fan: axial.
Material:
housing: stainless steel,
combustion chamber: stainless steel,
burner control unit: flame-retardant polymer blend
made of polycarbonate (PC) and acrylonitrile
butadiene styrene copolymer (ABS).
Ambient temperature T
max.
: ≤ 40°C,
temperature differential ∆T
max.
: ≤ 35°C,
example for calculating the jet temperature:
T + ∆T = 40°C + 35°C = 75°C.
Storage temperature: -20 to +50°C.
Cycle lock: 15 s.
Capacity: 40 kW.
Jet length: 40 m,
velocity at the jet end: 0.5 m/s.
Gas consumption:
natural gas L: 4.4 m
3
/h,
natural gas H: 3.7 m
3
/h,
propane: 2.7 kg/h,
butane: 3.1 kg/h.
Connection rating:
230 V AC, -15/+10%, 50 Hz, 100 W.
Current consumption I
A
/I
N
: ±2.0 A/0.6 A.
Air circulation:
controlled air flow: ± 3300 m
3
/h,
heating: ± 3900 m
3
/h.
Dimensions: 1200 x 600 x 440 mm.
Sound level: ≤ 68 dB.
Weight: 25 kg.
The Netherlands
The device has been designed for equipment cat-
egory K (I2K) and is suitable for use with distribution
gases G- and G+ in accordance with the specifica-
tions set out in NTA 8837:2012, Annex D, with a
superior Wobbe index of 43.46 – 45.3 MJ/m
3
(dry,
0°C) or 41.23 – 42.98 (dry, 15°C).
In addition, this device can be converted to equip-
ment category E (I2E) and/or calibrated.
This means the device is “suitable for G+ gas and H
gas or proven to be suitable for G+ gas and proof
has been provided that it can be converted for use
with H gas” as defined by the “Dutch Decree of 10
May 2016 regarding amendment of the Dutch Gas
Appliances Decree ...”.
Declaration of conformity
We, the manufacturer, hereby declare that the prod-
uct GP complies with the requirements of the listed
Directives and Standards.
Directives:
– 2014/30/EU – EMC
– 2014/35/EU – LVD
Regulation:
– (EU) 2016/426 – GAR
Standards:
– EN 525:2009
– EN 60335-1:2012
– EN 60335-2-102:2016
– EN 55011:2016
– EN 61000-6-2:2016
– EN 50465:2015
The relevant product corresponds to the tested type
sample.
The production is subject to the surveillance proce-
dure pursuant to Regulation (EU) 2016/426 Annex III,
No. 2, Module C2.
Elster-Instromet B.V.
Scan of the Declaration of conformity (D, GB) – see
www.docuthek.com
Logistics
Transport
Protect the unit from external forces (blows, shocks,
vibration). On receipt of the product, check that the
delivery is complete, see page 2 (Part designa-
tions). Report any transport damage immediately.
Storage
Store the product in a dry and clean place.
Storage temperature: see page 23 (Technical data).
Storage time: 6 months before using for the first
time. If stored for longer than this, the overall service
life will be reduced by the corresponding amount of
extra storage time.
Packaging
The packaging material is to be disposed of in ac-
cordance with local regulations.
Disposal
Components are to be disposed of separately in
accordance with local regulations.