INSTALLATION - DOOR CONFIGURATION
40
Installation guide
5
TECH. SUPPORT MENU (
+
+
)
SETUP
SETUP
The door performs a RESET and a normal movement: one opening and one
closing. The door will switch to AUTOMATIC mode once the configuration is
complete.
Default Parameters
All configured parameters are deleted and a guided CONFIGURATION starts in
order to establish the door's default parameters.
Guided SETUP
A guided CONFIGURATION starts in order to establish the door's basic
parameters for correct use. The door performs a RESET and a normal movement:
one opening and one closing. The door will switch to AUTOMATIC mode once
the configuration is complete.
Basic functions
Type of
door
Low Energy
The operator can be configured according to the low power operation
requirements of Standard EN 16005. The drive parameters are adjusted
according to the specifications of the respective standard. The required safety of
the system will be achieved by limiting the following characteristics:
•
Dynamic impact force.
•
Low speeds.
•
Reduction of static forces.
•
Limitation of force.
Due to the system's tolerances, actual forces in the door panel must be measured
after configuring the door in low energy mode, modifying any parameters
necessary in order to comply with the standards.
No additional safety sensors are required; they are optional.
Protection of the secondary closing edge should be considered
separately.
Full
Energy
(default
value)
Normal
(default
value)
The entire range of opening and closing speed parameters, along with opening
and closing torque, can be adjusted in Full Energy mode.
Safety sensors must be installed in order to comply with Standard
16005.
Fire Door This is a specific operation mode for fire doors according to Standard EN 14637.
The sensors detect the smoke and disable automatic opening of the door in the
event of fire. In this case, the operator will close the door using the built-in spring
and it will not open again automatically. Apart from activation by smoke
detector, the system can be triggered manually using a pushbutton. The operator
must be RESET in order to re-enable the system.
Type of
Arm
Articulated - Push
Articulated arm, opening toward the opposite side of the operator (code APR02)
Rigid - Pull
(default
value)
Rigid arm, opening toward the operator (code APR01)
Rigid - Push
Rigid arm, opening toward the opposite side of the operator (code APR01)
Opening
Direction
Toward the
operator
(default
value)
Door opening direction toward the operator
Toward the other
side of the operator
Door opening direction toward the opposite side of the operator
Operator
position
Lintel
(default value) Operator position on the lintel.
Door
Operator position on the door.