General connections
Turning direction:
check operation using the
mini-pushbuttons PUL1 (close) and PUL2 (open).
If the turning direction of the operator is not
correct, interchange the cables connected in
cable connectors G1 and G2.
O p e r a t o r
connections A:
G1
open
G2
close
G3
common,
grey
T:
earth
connection
•
When pressing PUL1 (close), DL5 lights up
and the G2 and G3 cable connectors of the
operator are enabled.
•
When pressing PUL2 (open), DL4 lights up
and the G1 and G3 cable connectors of the
operator are enabled.
VIVO-M101:
230Vac/50Hz
VIVO-M101M:
125Vac/60Hz
DEST.
(max. 40W)
VIVO-M101: 230Vac
VIVO-M101M: 125Vac
LG
VIVO-M101: 230Vac, max 2,300W
(resistive)
VIVO-M101M: 125Vac, max 1,250W
(resistive)
VIVO-M101: 230Vac
VIVO-M101M: 125Vac
PUL1:
close
mini-pushbutton
PUL2:
open
mini-pushbutton
DL1
Gate totally or partially open
DL1 - DL3 flashing:
STOP contact
o p e n ( e m e r g e n c y s t o p
activated)
DL2
Receiving RSD plug-in receiver
radio signal (RUN/OK)
DL3
Radio code or operation
programming
DL4
Opening relay activated
DL5
Closing relay activated
DL6
Interior safety device contacts
(FT2) closed
DL7
FCA contacts closed
DL8
FCC contacts closed
DL9
Exterior safety device contacts
(FT1) closed
DL10
Pedestrian key command (ST2)
DL11
Total key command (ST1)
DL12
Plug-in receiver key command
(except RSD)
DL13
Garage light relay activated
DL14
Power supply
DL15
Electrolock relay activated
DL17
Triac M1 activated
Fuses:
F1
M1 Motor fuse
– M101: 2,5A (230Vac/50Hz)
– M101M: 6,3A (125Vac/60Hz)
F2
Electronic fuse
– M101: 0,5A (230Vac/50Hz)
– M101M: 1A (125Vac/60Hz)
F3
Output fuse 24Vac (315mA)
DIP1=ON
: programming enabled (DL3 lights up)
DIP1=ON and DIP2=ON
: total open/close programming
DIP1=ON and DIP3=ON
: pedestrian open/close programming
DIP1=ON and DIP4=ON
: total opening radio code programming
DIP1=ON and DIP6=ON
: pedestrian opening radio code programming
SW2 Functions during programming (DIP1=ON)