10. Fault Diagnosis
Problem
Likely cause
No Indication
Supply connections not as per connection
diagram or no Supply voltage .
Over range
Sensor not connected
Sensor not connected properly.
Sensor Open
Irrelevant
Indication
Loose Sensor Connections
Noise pickup on sensor / sensor cable
Excessive Abmbient temperature
Improper sensor type
Fluctuations in
Indication Or
Setpoint not steady
Supply voltage not within specified limit.
Excessive Abmbient temperature
Error in
Indication
Improper Sensor Location
Improper Sensor type
Calibration error.
Excessive Abmbient temperature
Commonly observed problems and their likely causes. Please read
Installation Procedure and Instrumentation health prior to this.
In case the problem persists, please refer the service manual of the product
or get in touch with our Customer Support division.
No relay
Output
Improper Setpoint
Changeover tracks on PCB burnt due to
overload
Relay faulty
Temp. Overshoot/
Undershoot
Relay chattering
Improper Sensitivity Adjustment