Technical Data
Manual • Doc.-No.: C.3012.21 / Rev. 1.1 CAN-CBX-REL4
Page 12 of 99
2.4 Relay-Connection
Number
2 relays with monostable change over contacts,
2 relays with monostable normally open contacts
Relay type
OMRON G6C-211x
Max. switching voltage
250 VAC, 125 VDC
Max. switching current
8 A (AC and DC)
Max. switching power
resistive load:
2000 VA / 240 W;
inductive load: 875 VA / 170 W
Max. switching
frequency
30 operations per minute
Endurance mechanical
load
100 000 cycles
Table 4: Relay
2.5 Software-Support
The firmware of the module supports CANopen
®
according to CiA
®
CANopen profile CiA 301 [1] and
CiA DS-401 [2].
The CAN-CBX-REL4 EDS file can be downloaded from the esd website
www.esd.eu
.