Implemented CANopen Objects
Manual • Doc.-No.: C.3012.21 / Rev. 1.1 CAN-CBX-REL4
Page 68 of 99
7.9.17 Producer Heartbeat Time (1017
h
)
INDEX
1017
h
Name
producer heartbeat time
Data type
unsigned 16
Default value
0 ms
The producer heartbeat time defines the cycle time with which the CAN-CBX- module transmits a
heartbeat-frame to the node-guarding ID.
If the value of the producer heartbeat time is higher than ‘0’, it is active and stops the node-/ life-
guarding (see page 58).
If the value of the producer-heartbeat-time is set to ‘0’, transmitting heartbeats by this module is
stopped.
Index
Sub-
index
Description
Value range
Default
Data type
Access
mode
1017
h
0
producer-
heartbeat_time
0...FFFF
h
0 ms
unsigned 16
rw
producer-heartbeat_time Cycle time [ms] of heartbeat producer to transmit the heartbeat on the
node-guarding ID (see object 100E
h
).
The consumer-heartbeat time of the monitoring module must always be
higher than the producer-heartbeat time of the heartbeat-transmitting
module.