Parameter Display and Configuration via
CICT
CAN-CBM-DP
Software Manual Rev. 2.0
73
SYNC Time:
The CAN-CBM-DP module can cyclically transmit the commands SYNC and
START for simple CANopen applications. The
SYNC Time
for the transmission
can be specified in the properties window, via the Communication Window or
via the tool
CICT
as described above.
The specified cycle is used for the SYNC command as well as the START
command. It is specified in milliseconds.
SYNC Time
is specified as a decimal value, here.
Parameter
Value range
[dec] in [ms]
Explanations
SYNC Time
0
No SYNC and Start transmissions possible
1...65534
SYNC Time and Start Time in milliseconds
(1...65534 ms)
65535
Use current value from gateway (default)
Table 7.2.3:
Function of parameter
SYNC Time
Attention:
SYNC Time
can be set in three different ways:
1. As described above.
2. Via the parameter telegram in the DP properties windows (refer to
page 23)
3. Via bytes 4 and 5 of the Communication Window (refer to page 37).
All three specifications are equal. That means that the last specification is
valid!
CAN Bit Rate
In program
CICT
the CAN bit rate can only be read. The CAN bit rate is set by
means of the configuration telegram as described on page 23.