background image

 

 

 

 

 

* if the sensor or actuator supports Auto-E-Connect. For details, please refer to the operating instructions of the sensor or actuator. 
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of 
ESERA GmbH. Errors and technical modification subject to change. 



ESERA GmbH 2021 

www.esera.de 

11216 V5.0 R1.0 Manual 

Page 1 of 9 

Art. No. 11216 

 
 
 
 

User Guide 

8-fold Digital Input for 1-Wire Bus 

 

 

 

  8 inputs for 10-30V DC signals   

e.g. for switches, reed contacts or other  
digital sensors 

  LED displays for input status,  

and supply voltage 

  Inputs can be activated by manual operation  

  DIN rail housing for control cabinet installation  

  Connection via screw terminals  

  Simple software integration  

  1-Wire interface DS2408 commands 

  Housing color green (RAL 6020) 

 
 
 
 
 
 
 
 
 
 
 

 

 

 

Note 

Before you start assembling the device and put it into operation, read this operating manual through 
to the end at your leisure, especially the section on safety instructions.   
 

Summary of Contents for 11216

Page 1: ...of 9 Art No 11216 User Guide 8 fold Digital Input for 1 Wire Bus 8 inputs for 10 30V DC signals e g for switches reed contacts or other digital sensors LED displays for input status and supply voltage Inputs can be activated by manual operation DIN rail housing for control cabinet installation Connection via screw terminals Simple software integration 1 Wire interface DS2408 commands Housing color...

Page 2: ...ion of the Module only a 2V supply voltage is necessary For this we recommend the use of one of our 1 Wire Hub module 2 Technical Data Number and Type 8 inputs for DC voltage signals 10 30VDC Input voltage max 30 VDC max 8mA low level 5V high level 10 30V Filter Software filter against switch bounce 30 ms delay LED displays 10 LEDs Power LED Status LED 8 x Input Input LED lights up at status high ...

Page 3: ...rmatted data is output The Auto E Connect functionality will be available for the ECO Controller and ESERA Station 200 Pro from 2021 Auto E Connect Level I OWD Detect detection of new sensors and actuators and automatic start of adapted libraries Auto E Connect Level II Visualisation product data reading out and visualising of the Auto E Connect and manufacturer data of sensors and actuators e g a...

Page 4: ...ound 2 1 Wire 3 12V voltage Note The module may only be operated at the voltages and under the ambient conditions specified for it The operating position of the device is arbitrary The modules may only be commissioned by a qualified electrician For further information on the operating conditions see the following instructions under Operating conditions Note on switching loads When switching capaci...

Page 5: ... as electronic duplication of this user guide complete or in part requires the written consent of ESERA GmbH Errors and technical modification subject to change ESERA GmbH 2021 www esera de 11216 V5 0 R1 0 Manual Page 5 of 9 Art No 11216 8 Connection example Here is a connection example with 1 Wire Controller or 1 Wire Gateway Dual Digital Output and 8 fold Digital Input ...

Page 6: ...n press for 2 seconds activation of Manual Mode for setting the inputs after that selection of the input to be set by pressing briefly Pushbutton 2 ON OFF the pushbutton has a double function input on off in Manual Mode by pressing briefly press for 2 seconds deactivates Manual Mode for all manually set inputs 10 Software Control The 1 Wire interface of the module is read out via 1 Wire command fo...

Page 7: ... linear topology can be compared like pearls on a pearl necklace The data line should be laid from one device to the next without T joints Furthermore the type of cable used can also be mentioned here We recommend for the cabling CAT5 or CAT6 network cable It is also possible to use J Y St Y telephone cables and KNX cables Longer cable runs are possible with CAT5 versus CAT7 cables With twisted pa...

Page 8: ...lly suitable for the application in which it is to be used In case of doubt consultation with experts or the manufacturer of the components used is absolutely necessary For operational and connection errors outside of our control we assume no liability of any kind for any resulting damage Kits should be returned without their housing when not functional with an exact error description and the acco...

Page 9: ...r titles or legally protected designations of their respective owners and are hereby expressly recognized as such by us The mention of these designations logos names and trademarks is made for identification purposes only and does not represent a claim of any kind on the part of ESERA GmbH on these designations logos names and trademarks Moreover from their appearance on ESERA GmbH webpages it can...