*if the sensor or actuator supports Auto-E-Connect. For details, please refer to the operating instructions of the sensor or actuator.
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change.
ESERA GmbH 2021
www.esera.de
11216 V5.0 R1.0 Manual
Page 2 of 9
1
Product description
The 8-fold Digital Input Module can be used to query the status of 8 switches, reed contacts or all kinds of digital
sensors. The LED indicators on the front panel show the status of the switch inputs. When the input voltage is
present, the respective LED indicator lights up.
To protect the inputs additionally against disturbances, the module has filters with a delay of only 30ms.
Each input can be set manually by pushbutton for test purposes, maintenance or development.
The inputs are isolated from the 1-Wire Network by Optocouplers. This allows very long connection cables
between the module and the sensors without interfering with the 1-Wire Bus.
In addition, the isolation between switch inputs and 1-Wire Network provides increased safety.
For the operation of the Module only a 2V supply voltage is necessary. For this, we recommend the use of one
of our 1-Wire Hub module.
2
Technical Data
Number and Type
8 inputs for DC voltage signals 10 - 30VDC
Input voltage
max. 30 VDC, max.8mA, low level: <5V high level 10-30V
Filter
Software filter against switch bounce (30 ms delay)
LED displays
10 LEDs (Power LED, Status LED, 8 x Input)
Input LED lights up at status high of the 1-Wire DS2408 interface
Data interface
1-Wire Bus (12V, Data and ground), DS2808 command set
Auto-E-Connect
Support
Level I to II
Operating voltage
12VDC (+/-10%)
Current
consumption 12V
12V: max. 40mA, all inputs active
Internal fuses
no changeable fuses available
Insulation voltage
min. 500VAC against 1-Wire Bus
Connection
srew terminals (up to 2,5qmm cable cross section)
3
Ambient conditions
Temperature,
Operation
-10°C to +50°C
Air humidity
10 - 92% (non condensing)
Dimensions
32 x 90 x 70mm (WxHxD)
Protection class
II
Protection system
IP20
Auto-E-Connect
Support
Level I to II
Insulation
resistance
500VAC inputs to 1-Wire Bus
Note
Basics and Tips on the 1-Wire Bus system can be found in the ESERA Online Shop under
1-Wire Basics or please refer to our eBook in the shop under Training/Documentation.
Note
Only a 12V supply voltage is required to operate the module.
For power supply we recommend a 1-Wire Hub device. Input voltages above 30V can cause permanent
damage to the module.