4…20mA signal calibration mode
To execute this type of calibration, it is necessary to insert in series to the 4...20mA output an
instrument suitable for this magnitude and with a precision of at least 2% on the full scale.
Calibration consists of calibrating two points (one at 4mA, the other at 15 mA)
During the warm-up phase only, enter the monitoring mode and press
9
to enter a menu
where it is possible to directly test the relay outputs, or press
0
to enter the 4…...20mA
output calibration procedure.
The display will show the following:
The two fields XXXX are the A/D Converter values required to generate the output currents.
Press: or to vary the output that generates the 4mA with a delay of about 2
seconds.
Press the key to memorise calibration; the display will show that the new value has been
saved by changing as follows:
Press: or to vary the output that generates the 15mA with a delay of about 2
seconds.
Otherwise, press to terminate the procedure without memorising the new value.
C a l i b . 4 - 2 0 m A : 4 m A
4 = X X X X 1 5 = X X X X
Fig. 4.21
C a l i b . 4 - 2 0 m A : 1 5 m A
4 = X X X X 1 5 = X X X X
Fig. 4.22