MAGPRO16 Addressable Fire Alarm Panel – Installation and Programming Manual
19
Use the
Windows Explorer
file manager to copy the new image update file (with *.bin extension) in
Removable
Disk
directory.
When the copying of the image file completes, remove the
Removable Disk
, as select
Eject
option from its
dialogue box (right click with the mouse over it).
If the data in the image file are correct, the panel starts the firmware update procedure of the main
microprocessor accompanied with short beeps.
Disconnect the USB cable.
The panel will reset itself automatically after a successful firmware update.
3.3.2 Firmware Update from USB Drive
To start a firmware update from a USB drive you should first have to copy the new image update file (with
*.bin
extension) in the main directory of the USB removable disk. The name of the file must be short
– up to 8 symbols.
Connect the panel to the computer using USB cable:
USB Micro А - USB A type.
Enter access code for level 2 or 3 and choose menu
9) SOFT. REVISION.
Connect the USB drive, with the new image file (with
*.bin
extension).
Notes:
1. The panel will scan the files copied only in the main directory and these files in the first subfolders in the tree
hierarchy of the USB drive.
2. It is obligatory the name of the file to be up to 8 symbols long.
Wait until the polling procedure is complete - USB drive will be displayed with its name and manufacturer. On
the last row of the screen will start blinking the notice
Push 'Enter' to continue
.
Press
Enter
button and wait for a message for the USB drive capacity. On the last row of the screen will be
active two buttons
(2) To Panel
and
(3) From Panel.
Press
(2) To Panel
button. A list with the present image files (with
*.bin
extension) copied to USB drive is
displayed on the screen, as the software revision is displayed on the right side, for example:
0:/MAGPRO16/MAGPRO162_0.BIN v 2.00
Scroll through the listed files using the buttons with up and down arrows
– the currently selected file is blinking.
Select the file and press
Enter
button.
The panel starts uploading the file from the USB drive to the external Flash memory of the panel. The running
process is displayed with a progress bar.
If the data in the image file are correct, the panel starts the firmware update procedure of the main
microprocessor accompanied with short beeps.
Disconnect the USB cable.
The panel will reset itself automatically after a successful firmware update.
3.3.3 Copying Image File from the Panel to USB Drive
Connect the panel to the computer using USB cable: USB Micro B - USB A type.
Enter access code for level 2 or 3 and choose menu
9) SOFT. REVISION.
Connect the USB drive.
Wait until the polling procedure is complete - USB drive will be displayed with its name and manufacturer. On
the last row of the screen will start blinking the notice
Push 'Enter' to continue
.
Press
Enter
button and wait for a message for the USB drive capacity. On the last row of the screen will be
active two buttons
(2) To Panel
and
(3) From Panel.
Press
(3) From Panel
button
– the panel will download a copy of its own image file to the USB drive and saves
the file in MAGPRO16 folder.
4. FULL HARDWARE RESET
The full hardware reset of MAGPRO16 addressable fire alarm panel allows the engineer to restore all factory settings
and access code combinations for level 2 (Maintenance) and 3 (Installer).
To perform full hardware reset, follow the steps:
1. Disconnect the mains and backup power supplies.
2. Set a jumper on
‘RESTORE DEFAULTS’ terminal on the PCB.
3. Connect mains and after that the backup power supply.
4. Wait the procedure for initialization to complete.
5. Remove the jumper from
‘RESTORE DEFAULTS’ terminal.
6. Proceed with save system configuration and other settings.