MAGPRO16 Addressable Fire Alarm Panel – Installation and Programming Manual
24
After choosing the button (2) TESTS the screen displays
:
To exit the review of running tests mode, press CANCEL button.
6.5. Review of Warning Messages
The messages for warnings are displayed with low priority. If no alarm or fault events or disablements and tests are
present, and there are active warnings in the system, the WARNINGS mode is blinking together with the number of the
first message. There is no LED indication on the front panel.
Example:
The User can review also some additional information for every warning message. For this, select the number of the
message using up/ down arrow buttons (the number of the selected event is blinking) and press ENTER button. On the
screen is displayed information for the loop number and the address of the device. At the bottom of the screen is
displayed the day and time of occurring of the warning. Note that the additional information is different according the
type of the warning event.
In case, there are active alarms and/ or faults in the system, but you want to review the warnings, press button (4)
MORE>>
– (3) WARNING mode. The warning messages in the system are displayed with serial numbers. The
reviewing is the same as described in item 6.1. The total number of the warnings is displayed at the bottom right corner
of the screen. Use button (1) to go back to ALARMS mode and reviewing the alarm messages.
To review the WARNINGS at active alarms and/ or faults in the system:
After choosing the button (3) WARNINGS the screen displays
:
To exit the review warning messages mode, press CANCEL button.
NOTE:
If you are programming parameters at Access Level 2 (Maintenance) or Access Level 3 (Installer) and there is
an alarm or fault event in the system, the panel will automatically display a list with messages. After reviewing the
events, you can return to the programming mode with single pressing the CANCEL button.