MAGPRO16 Addressable Fire Alarm Panel – Installation and Programming Manual
5
1. INTRODUCTION
1.1. General Description
MAGPRO16 is an addressable fire panel with maximum coverage of 16 zones and connecting and up to 2 loops. The
panel supports communication protocol
MAGPRO (MAGPRO16-L250 Loop)
and operation with MAGPRO
addressable device series.
Every MAGPRO16-L250 Loop provides up to 250 devices (detectors and modules, regardless of the
type).
An arbitrary number of devices can be added to each zone thus ensuring the easy adaptation of the system to any type
of configuration.
To avoid or significantly diminish problems when mounting the system it must be carefully planned prior to installation.
This includes: setting an address for every device and planning a name of maximum 40 digits (including the
spaces) for each address, thereby ensuring easy access to the device.
According to the acting standards for establishing fire systems and the plan of the building, the devices must
be grouped in zones.
1.2. General Specifications
The front panel consists of LCD module (4 rows x 40 symbols), functional buttons and system status LED indication.
Separate access level passwords provide access to the functions of the panel.
The fire alarm panel is designed on module structure as in the metal cabinet there are provided additional places for
mounting of a second loop controller for Loop 2 (Loop 1 is built-in the main PCB), LAN module and redundant network
module.
The panel has a built-in real time clock and calendar, allowing day and night time modes of work.
Switching over between the two modes can be automatic or manual. Events like FIRE, RESET, FAULT, etc., are saved
in the memory, thereby creating an event log-file. It contains the time and date, the address of the device, the name of
the device, the zone number, the name of the zone, etc.
1.2.1 General Technical Specifications
Loops - 1 to 2:
o
Loop 1 is built-in in the main board
o
Loop 2
– optional, separately mounted to the main control panel
Number of loop devices:
o
Up to 250 devices (modules and/ or detectors regardless of the type) for every loop (max. 500 for the
entire system)
16 operation zones