Keypad Configuration
Voltage Selection
The factory default setting for the Keypad voltage is 12-24VDC.
Verify that the jumper is removed or placed over only one pin. For
5VDC, the jumper should be placed across both pins. If changing
the voltage is necessary, make sure the power is removed first.
Keypad Output Selection
ThE KEYPAD OUTPUT IS fACTORY CONfIGURED AND DOES
not nEED to BE REConfIguRED In thE fIELD.
Once the voltage jumper is verified or correctly set (see above):
1. Remove power.
2. Jumper the two pins above the connector labeled “CONFIG.”
3. Apply appropriate power. (You should hear 4 beeps and the
RED LED will flash and the GREEN LED will be solid).
4. Now that the Keypad is in configuration mode, select the de-
sired output by entering the configuration number followed by #.
a. Keypad Output
Keypad Output
Configuration
Self-Contained- Non-encoded
99 #
b. (OPTIONAL) To change the audible beep, enter
Code Audible Beep
201 # Normal Beep (factory default)
200 # Short Click (quieter)