Installation
LSS4 Field Wiring
The total length of the RS-485 communications loop used to connect
multiple annunciators when used with an LSS4 panel cannot exceed
4,500' (1372 M) in total length, based on #18 AWG twisted-pair wire.
Note:
The terminals on the annunciators cannot accept wire greater
than #18 AWG.
Wire the annunciators per the figures that follow. The table below lists
these connections.
Table Chapter 3-2: Annunciator LSS4 Terminal Connections
TERM Function
Connect
to
TB1-1 Enable/Disable
Sw
(+) External Key switch-open switch
disables panel, requiring password
(not supervised)
TB1-2 Enable/Disable
Sw
(-) External Key switch-open switch
disables panel, requiring password
(not supervised)
TB1-3
RS-485, Ch 0 (+)
From LSS4, RS-485E (+), To/From
Term #7 of additional LSRA(-C)
TB1-4
RS-485, Ch 0 (-)
From LSS4, RS-485E (-), To/From
Term #8 of additional LSRA(-C)
TB1-5
RS-485, Ch 1 (+)
Not Used
TB1-6
RS-485, Ch 1 (-)
Not Used
TB1-7
+ 24 VDC
+ 24 VDC Power Supply
TB1-8
24 VDC Common
24 VDC Common Power Supply
TB1-9 Earth
Ground
Local earth ground
RJ-11
WHT
RS-232, Common
RS-232 - Common on printer
(To common on PC serial port when
downloading) (not supervised)
RJ-11
RED
RS-232 T
X
Out
RS-232 - Rx In on printer
(To data Rx on PC serial port when
downloading) (not supervised)
RJ-11
YEL
RS-232 Rx In
RS-232 - Tx Out on printer
(To data Tx on PC serial port when
downloading) (not supervised)
Note:
Refer to Figure Chapter 3-3 for RJ-11 Wiring Color Code.
EOL Resistor Installation
UL listed 100 Ohm EOL resistors (P/N 260071 or EOL-100) are used
to terminate the RS-485 circuit. The RS-485 terminating EOL resistor
should be installed ONLY at the last physical connection location on
the data line.
3.10
LSRA
Installation, Operation, Maintenance, and Configuration Manual
firealarmresources.com
Summary of Contents for LSRA
Page 10: ...firealarmresources com ...
Page 14: ...firealarmresources com ...
Page 36: ...firealarmresources com ...
Page 82: ...firealarmresources com ...
Page 86: ...firealarmresources com ...