Programming
Base Address (s) (IRC-3 only)
The lowest address assigned to a LSRA on an IRC-3 (FCC/PCPU)
system. Up to four consecutive addresses may be assigned to each
display. Assign the base address so as to avoid network address 41,
which is dedicated for ACP/FCCA applications. Each network address
equals 88 messages.
Baud Rate
The parameter which sets the baud rate on the local LSRA’s optional
LSRA-232 Printer/Programming port. Baud rate options can be directly
entered using the figures “2,” “4,” & “9,” i.e. valid options are
{
2400
}
,
4800, and 9600. Do not confuse this setting with the “network” or
“communications” baud rates.
Communication Baud Rate (LSS4, IEC-3 only)
The parameter which sets the Life Safety Remote Annunciator
Network’s data transfer rate. Valid entries are:
FCC: 2400, 4800,
{
9600
}
, 19200
IRC-3: 2400, 4800,
{
9600
}
LSS4:9600 (not selectable)
Current Message (MSG)
Current message window shows an arbitrary index of the relative
location of the currently entered message in the displayed LSRA's
memory.
Fault Action (FCC Only)
The parameter which assigns an FCC action to be activated when the
Life Safety Remote Annunciator Network has a fault condition. Valid
entries are 0001 to 9999
{
8999
}
.
FCC Text (FCC Only)
When “ON”, causes LSRA to request message text from FCC/DCPU.
Master LSRA must be set “ON” for slave LSRAs to operate in this
mode. A maximum of 5 displays can be set in this mode.
Geographic Category
The parameter which sets parameters depending on installation
location. Each area requires slightly different operation of indicator
LEDs and the trouble buzzer.
Line
The IRC-3 or FCC network data line address.
4.24
LSRA
Installation, Operation, Maintenance, and Configuration Manual